Carrier 48/50AJ specifications Fans in Service Test Mode — Upon entering the

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 30
Image 30

However, it is important to note that the user can leave a Service Test mode to view any of the local display modes and the control will remain in the Service Test mode.

Independent Outputs — The INDP sub-mode items can be turned on and off regardless of the other category states. For example, the alarm relay can be forced on in the INDP sub-mode and will remain on if compressor relays are request- ed in the COOL sub-mode.

Fans in Service Test Mode — Upon entering the

FANS sub-mode, the user will be able to turn the supply fan on and off, set the supply fan VFD speed, and turn the condenser fans on and off.

Cooling in Service Test Mode — The COOL sub- mode offers different cooling service tests.

The user has manual relay control of individual compres- sors. If the user energizes mechanical cooling, the supply fan and the outdoor fans will be started automatically. During mechanical cooling, the unit will protect itself. Compressor diagnostics are active, monitoring for high discharge pressure, low suction pressure, etc. The user can also turn the hot gas bypass valve on and off.

NOTE: It is crucial that proper compressor rotation be verified during the service test. Each compressor must be tested

individually. After starting each compressor, the control will check the suction pressure after 5 seconds of run time. If the control does not see a sufficient decrease in suction pressure after 5 seconds, mechanical cooling will be shut down, and an alarm will be generated (A140). This alarm requires a manual reset. If this alarm occurs, do not attempt a restart of the compressor and do not attempt to start any other compressors until the wiring to the unit has been corrected.

Heating in Service Test Mode — If unit has a ther- mostat connected (C.TYP = 3 or 4), install the RED jumper wires between TB4, terminals R (1), W2 (3) and W1 (4). Ter- minal block TB4 is located in the unit control box. Remember to disconnect these jumpers when Test Mode is completed. The Heat Test Mode sub-mode will offer automatic fan start-up if the unit is not a gas heat unit. On gas heat units, the IGC feed- back from the gas control units will bring the fan on as required.

Within this sub-mode, the user has control of heat relays 1 to 6. The user can also turn on the requested heat stage.

NOTE: When service test has been completed, if unit has a thermostat connected (C.TYP = 3 or 4), remove the RED jumper wires at TB4, terminals R (1), W2 (3) and W1 (4). Terminal block TB4 is located in the unit control box. Store these jumpers in the unit control box for future use.

Table 41 — Service Test

ITEM

EXPANSION

 

RANGE

UNITS

POINT

WRITE STATUS

TEST

Service Test Mode

 

ON/OFF

 

MAN_CTRL

 

STOP

Local Machine Disable

 

YES/NO

 

UNITSTOP

config

S.STP

Soft Stop Request

 

YES/NO

 

SOFTSTOP

forcible

FAN.F

Supply Fan Request

 

YES/NO

 

SFANFORC

forcible

F.4.CH

4 in. Filter Change Mode

 

YES/NO

 

FILT4CHG

 

INDP

TEST INDEPENDENT OUTPUTS

 

 

 

 

 

ECON

Economizer Act.Cmd.Pos.

 

 

 

ECONCTST

 

 

 

 

 

E.PWR

Economizer Power Test

 

 

 

ECONPTST

 

E.CAL

Calibrate the Economizer?

 

 

 

ECON_CAL

 

E.VFD

Exhaust Fan VFD Speed

 

0-100

%

EFAN_VFD

 

PE.A

Power Exhaust Relay A

 

 

 

PE_A_TST

 

PE.B

Power Exhaust Relay B

 

 

 

PE_B_TST

 

PE.C

Power Exhaust Relay C

 

 

 

PE_C_TST

 

H.I.R

Heat Interlock Relay

 

ON/OFF

 

HIR_TST

 

ALRM

Remote Alarm/Aux Relay

 

ON/OFF

 

ALRM_TST

 

FANS

TEST FANS

 

 

 

 

 

S.FAN

Supply Fan Relay

 

ON/OFF

 

SFAN_TST

 

 

 

 

S.VFD

Supply Fan VFD Speed

 

0-100

%

SGVFDTST

 

CD.F.A

Condenser Fan Circuit A

 

ON/OFF

 

CNDA_TST

 

CD.F.B

Condenser Fan Circuit B

 

ON/OFF

 

CNDB_TST

 

COOL

TEST COOLING

 

 

 

 

 

A1

Compressor A1 Relay

 

ON/OFF

 

CMPA1TST

 

 

 

 

A2

Compressor A2 Relay

 

ON/OFF

 

CMPA2TST

 

MLV

Min. Load Valve (HGBP)

 

ON/OFF

 

MLV_TST

 

B1

Compressor B1 Relay

 

ON/OFF

 

CMPB1TST

 

B2

Compressor B2 Relay

 

ON/OFF

 

CMPB2TST

 

HEAT

TEST HEATING

 

 

 

 

 

HT.ST

Requested Heat Stage

 

0-MAX

 

HTST_TST

 

HT.1

Heat Relay 1

 

ON/OFF

 

HS1_TST

 

HT.2

Heat Relay 2

 

ON/OFF

 

HS2_TST

 

HT.3

Relay 3 W1 Gas Valve 2

 

ON/OFF

 

HS3_TST

 

HT.4

Relay 4 W2 Gas Valve 2

 

ON/OFF

 

HS4_TST

 

HT.5

Relay 5 W1 Gas Valve 3

 

ON/OFF

 

HS5_TST

 

HT.6

Relay 6 W2 Gas Valve 3

 

ON/OFF

 

HS6_TST

 

30