APPENDIX B — CCN TABLES

All A Series units with ComfortLink™ controls have a port for interface with the Carrier Comfort Network® (CCN) system. On TB3 there is a J11 jack which can be used for temporary connection to the CCN network or to computers equipped with CCN software like the Service Tool. Also on TB3 there are screw connections that can be used for more permanent CCN connections.

In the following tables the structure of the tables which are used with the Service Tool as well as the names and data that are included in each table are shown. As a reference the equiv- alent scrolling marquee tables and names are included. There are several CCN variables that are not displayed through the scrolling marquee and are used for more extensive diagnostics and system evaluations.

STATUS DISPLAY TABLES

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

COOLING

HVAC Mode…………..:

ascii text strings

 

 

 

 

 

 

 

 

Control Mode………..:

ascii text strings

 

 

 

 

Current Running Capacity

 

%

CAPTOTAL

 

 

Cooling Control Point

 

dF

COOLCPNT

 

 

Evaporator Discharge Tmp

 

dF

EDT

 

 

Mixed Air Temperature

 

dF

MAT

 

COOL_A

Compressor A1 Relay

 

 

CMPA1

 

 

 

 

 

 

Compressor A1 Feedback

 

 

CSB_A1

 

 

Compressor A1 Timeguard

 

 

CMPA1_TG

 

 

Compressor A2 Relay

 

 

CMPA2

 

 

Compressor A2 Feedback

 

 

CSB_A2

 

 

Compressor A2 Timeguard

 

 

CMPA2_TG

 

 

Minimum Load Valve

 

 

MLV

 

 

Cir A Discharge Pressure

 

PSIG

DP_A

 

 

Cir A Suction Pressure

 

PSIG

SP_A

 

 

Cir A Sat.Condensing Tmp

 

dF

SCTA

 

 

Cir A Sat.Suction Temp.

 

dF

SSTA

 

COOL_B

Compressor B1 Relay

 

 

CMPB1

 

 

 

 

 

 

Compressor B1 Feedback

 

 

CSB_B1

 

 

Compressor B1 Timeguard

 

 

CMPB1_TG

 

 

Compressor B2 Relay

 

 

CMPB2

 

 

Compressor B2 Feedback

 

 

CSB_B2

 

 

Compressor B2 Timeguard

 

 

CMPB2_TG

 

 

Cir B Discharge Pressure

 

PSIG

DP_B

 

 

Cir B Suction Pressure

 

PSIG

SP_B

 

 

Cir B Sat.Condensing Tmp

 

dF

SCTB

 

 

Cir B Sat.Suction Temp.

 

dF

SSTB

 

ECONDIAG

Economizer Active ?

Yes/No

 

ECACTIVE

 

 

 

 

 

Conditions which prevent

 

 

 

 

 

economizer being active:

 

 

 

 

 

Econ Act. Unavailable?

Yes/No

 

ECONUNAV

 

 

Remote Econ. Disabled ?

Yes/No

 

ECONDISA

 

 

DBC - OAT lockout?

Yes/No

 

DBC_STAT

 

 

DEW - OA Dewpt. lockout?

Yes/No

 

DEW_STAT

 

 

DDBC- OAT > RAT lockout?

Yes/No

 

DDBCSTAT

 

 

OAEC- OA Enth Lockout?

Yes/No

 

OAECSTAT

 

 

DEC - Diff.Enth.Lockout?

Yes/No

 

DEC_STAT

 

 

EDT Sensor Bad ?

Yes/No

 

EDT_STAT

 

 

OAT Sensor Bad ?

Yes/No

 

OAT_STAT

 

 

Economizer forced ?

Yes/No

 

ECONFORC

 

 

Supply Fan not on 30s ?

Yes/No

 

SFONSTAT

 

 

Cool Mode not in effect?

Yes/No

 

COOL_OFF

 

 

OAQ lockout in effect ?

Yes/No

 

OAQLOCKD

 

 

Econ recovery hold off?

Yes/No

 

ECONHELD

 

ECONOMZR

Economizer Act.Curr.Pos.

 

%

ECONOPOS

 

 

 

 

 

Economizer Act.Cmd.Pos.

 

%

ECONOCMD

forcible

 

Economizer Active ?

 

 

ECACTIVE

 

 

Economizer Control Point

 

dF

ECONCPNT

 

 

Outside Air Temperature

 

dF

OAT

forcible

 

Evaporator Discharge Tmp

 

dF

EDT

 

 

Controlling Return Temp

 

dF

RETURN_T

forcible

148

Page 148
Image 148
Carrier 48/50AJ specifications Appendix B CCN Tables, 148