APPENDIX A — LOCAL DISPLAY TABLES (cont)

MODE — CONFIGURATION (cont)

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

PAGE NO.

CCN

CCN CONFIGURATION

 

 

 

 

 

CCNA

CCN Address

1 - 239

 

CCNADD

1

71,72

CCNB

CCN Bus Number

0 - 239

 

CCNBUS

0

71,72

BAUD

CCN Baud Rate

1 - 5 (multi-text strings)

 

CCNBAUDD

3

71,72

BROD

CCN BROADCST DEFINITIONS

 

 

 

 

 

BRODTM.DT

CCN Time/Date Broadcast

ON/OFF

 

CCNBC

On

71,72

BRODOAT.B

CCN OAT Broadcast

ON/OFF

 

OATBC

Off

71,72

BRODORH.B

CCN OARH Broadcast

ON/OFF

 

OARHBC

Off

71,72

BRODOAQ.B

CCN OAQ Broadcast

ON/OFF

 

OAQBC

Off

71,72

BRODG.S.B

Global Schedule Broadcst

ON/OFF

 

GSBC

Off

71,72

BRODB.ACK

CCN Broadcast Ack'er

ON/OFF

 

CCNBCACK

Off

71,72

SC.OV

CCN SCHEDULES-OVERRIDES

 

 

 

 

 

SC.OVSCH.N

Schedule Number

0 - 99

 

SCHEDNUM

1

27-29,71,72

SC.OVHOL.T

Accept Global Holidays?

YES/NO

 

HOLIDAYT

No

72

SC.OVO.T.L.

Override Time Limit

0 - 4

HRS

OTL

1

27,72

SC.OVOV.EX

Timed Override Hours

0 - 4

HRS

OVR_EXT

0

72

SC.OVSPT.O

SPT Override Enabled ?

YES/NO

 

SPT_OVER

Yes

27,72

SC.OVT58.O

T58 Override Enabled ?

YES/NO

 

T58_OVER

Yes

27,72

SC.OVGL.OV

Global Sched. Override ?

YES/NO

 

GLBLOVER

No

72

ALLM

ALERT LIMIT CONFIG.

 

 

 

 

 

SP.L.O

SPT lo alert limit/occ

–10-245

dF

SPLO

60

72,73,98

SP.H.O

SPT hi alert limit/occ

–10-245

dF

SPHO

85

72,73,99

SP.L.U

SPT lo alert limit/unocc

–10-245

dF

SPLU

45

72,73,98

SP.H.U

SPT hi alert limit/unocc

–10-245

dF

SPHU

100

72,73,99

SA.L.O

EDT lo alert limit/occ

–40-245

dF

SALO

40

43,72,73,99

SA.H.O

EDT hi alert limit/occ

–40-245

dF

SAHO

100

72,73,99

SA.L.U

EDT lo alert limit/unocc

–40-245

dF

SALU

40

72,73,99

SA.H.U

EDT hi alert limit/unocc

–40-245

dF

SAHU

100

72,73,99

RA.L.O

RAT lo alert limit/occ

–40-245

dF

RALO

60

72,73,99

RA.H.O

RAT hi alert limit/occ

–40-245

dF

RAHO

90

72,73,99

RA.L.U

RAT lo alert limit/unocc

–40-245

dF

RALU

40

72,73,99

RA.H.U

RAT hi alert limit/unocc

–40-245

dF

RAHU

100

72,73,99

R.RH.L

RARH low alert limit

0-100

%

RRHL

0

72,73,99

R.RH.H

RARH high alert limit

0-100

%

RRHH

100

72,73,99

SP.L

SP low alert limit

0-5

"H2O

SPL

0

73,99

SP.H

SP high alert limit

0-5

"H2O

SPH

2

73,99

BP.L

BP lo alert limit

–0.25-0.25

"H2O

BPL

-0.25

73,99

BP.H

BP high alert limit

–0.25-0.25

"H2O

BPH

0.25

73,99

IAQ.H

IAQ high alert limit

0-5000

 

IAQH

1200

73,99

TRIM

SENSOR TRIM CONFIG.

 

 

 

 

 

SAT.T

Air Temp Lvg SF Trim

–10 - 10

^F

SAT_TRIM

0

73

RAT.T

RAT Trim

–10 - 10

^F

RAT_TRIM

0

73

OAT.T

OAT Trim

–10 - 10

^F

OAT_TRIM

0

73

SPT.T

SPT Trim

–10 - 10

^F

SPT_TRIM

0

73

CTA.T

Cir A Sat.Cond.Temp Trim

–30 - 30

^F

SCTATRIM

0

73

CTB.T

Cir B Sat.Cond.Temp Trim

–30 - 30

^F

SCTBTRIM

0

73

SP.A.T

Suct.Press.Circ.A Trim

–50 - 50

PSIG

SPA_TRIM

0

73

SP.B.T

Suct.Press.Circ.B Trim

–50 - 50

PSIG

SPB_TRIM

0

73

DP.A.T

Dis.Press.Circ.A Trim

–50 - 50

PSIG

DPA_TRIM

0

73,74

DP.B.T

Dis.Press.Circ.B Trim

–50 - 50

PSIG

DPB_TRIM

0

73,74

SW.LG

SWITCH LOGIC: NO / NC

 

 

 

 

 

FTS.L

Filter Status Inpt-Clean

Open/Close

 

FLTSLOGC

Open

74,75

IGC.L

IGC Feedback - Off

Open/Close

 

GASFANLG

Open

74,75

RMI.L

RemSw Off-Unoc-Strt-NoOv

Open/Close

 

RMTINLOG

Open

31,74,75

ECS.L

Economizer Switch - No

Open/Close

 

ECOSWLOG

Open

74,75

SFS.L

Fan Status Sw. - Off

Open/Close

 

SFSLOGIC

Open

74,75,100

DL1.L

Dmd.Lmt.Sw.1 - Off

Open/Close

 

DMD_SW1L

Open

31,74,75

DL2.L

Dmd.Lmt.Sw.2 - Dehumid - Off

Open/Close

 

DMD_SW2L

Open

31,74,75

IAQ.L

IAQ Disc.Input - Low

Open/Close

 

IAQINLOG

Open

31,32,74,75

FSD.L

Fire Shutdown - Off

Open/Close

 

FSDLOGIC

Open

74,75,99

PRS.L

Pressurization Sw. - Off

Open/Close

 

PRESLOGC

Open

74,75

EVC.L

Evacuation Sw. - Off

Open/Close

 

EVACLOGC

Open

74,75

PRG.L

Smoke Purge Sw. - Off

Open/Close

 

PURGLOGC

Open

74,75

DISP

DISPLAY CONFIGURATION

 

 

 

 

 

TEST

Test Display LEDs

ON/OFF

 

TEST

Off

74,75

METR

Metric Display

ON/OFF

 

DISPUNIT

Off

74,75

LANG

Language Selection

0-1(multi-text strings)

 

LANGUAGE

0

74,75

PAS.E

Password Enable

ENABLE/DISABLE

 

PASS_EBL

Enable

74,75

PASS

Service Password

0000-9999

 

PASSWORD

1111

74,75