Carrier 48/50AJ specifications CL-4

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 188
Image 188

ITEM

EXPANSION

RANGE

DEFAULT

ENTRY

AQ.S.RIQ.R.L

IAQ Low Reference

0 - 5000

0

 

AQ.S.RIQ.R.H

IAQ High Reference

0 - 5000

2000

 

AQ.S.ROQ.R.L

OAQ Low Reference

0 - 5000

0

 

AQ.S.ROQ.R.H

OAQ High Reference

0 - 5000

2000

 

IAQ.P

IAQ PRE-OCCUPIED PURGE

 

 

 

IAQ.PIQ.PG

IAQ Purge

Yes/No

No

 

IAQ.PIQ.P.T

IAQ Purge Duration

5-60 min

15

 

IAQ.PIQ.P.L

IAQ Purge LoTemp Min Pos

0-100 %

10

 

IAQ.PIQ.P.H

IAQ Purge HiTemp Min Pos

0-100 %

35

 

IAQ.PIQ.L.O

IAQ Purge OAT Lockout

35-70 dF

50

 

DEHU

DEHUMIDIFICATION CONFIG.

 

 

 

D.SEL

Dehumidification Config

0-2(multi-text strings)

0

 

D.SEN

Dehumidification Sensor

1-2(multi-text strings)

1

 

D.EC.D

Econ disable in DH mode?

Yes/No

Yes

 

D.V.CF

Vent Reheat Setpt Select

0-1(multi-text strings)

0

 

D.V.RA

Vent Reheat RAT offset

0-8 ^F

0

 

D.V.HT

Vent Reheat Setpoint

55-95 dF

70

 

D.C.SP

Dehumidify Cool Setpoint

40-55 dF

45

 

D.RH.S

Dehumidify RH Setpoint

10-90 %

55

 

CCN

CCN CONFIGURATION

 

 

 

CCNA

CCN Address

1 - 239

1

 

CCNB

CCN Bus Number

0 - 239

0

 

BAUD

CCN Baud Rate

1 - 5 (multi-text strings)

3

 

BROD

CCN BROADCST DEFINITIONS

 

 

 

BRODTM.DT

CCN Time/Date Broadcast

ON/OFF

On

 

BRODOAT.B

CCN OAT Broadcast

ON/OFF

Off

 

BRODORH.B

CCN OARH Broadcast

ON/OFF

Off

 

BRODOAQ.B

CCN OAQ Broadcast

ON/OFF

Off

 

BRODG.S.B

Global Schedule Broadcst

ON/OFF

Off

 

BRODB.ACK

CCN Broadcast Ack'er

ON/OFF

Off

 

SC.OV

CCN SCHEDULES-OVERRIDES

 

 

 

SC.OVSCH.N

Schedule Number

0 - 99

1

 

SC.OVHOL.T

Accept Global Holidays?

YES/NO

No

 

SC.OVO.T.L.

Override Time Limit

0 - 4 HRS

1

 

SC.OVOV.EX

Timed Override Hours

0 - 4 HRS

0

 

SC.OVSPT.O

SPT Override Enabled ?

YES/NO

Yes

 

SC.OVT58.O

T58 Override Enabled ?

YES/NO

Yes

 

SC.OVGL.OV

Global Sched. Override ?

YES/NO

No

 

ALLM

ALERT LIMIT CONFIG.

 

 

 

SP.L.O

SPT lo alert limit/occ

–10-245 dF

60

 

SP.H.O

SPT hi alert limit/occ

–10-245 dF

85

 

SP.L.U

SPT lo alert limit/unocc

–10-245 dF

45

 

SP.H.U

SPT hi alert limit/unocc

–10-245 dF

100

 

SA.L.O

EDT lo alert limit/occ

–40-245 dF

40

 

SA.H.O

EDT hi alert limit/occ

–40-245 dF

100

 

SA.L.U

EDT lo alert limit/unocc

–40-245 dF

40

 

SA.H.U

EDT hi alert limit/unocc

–40-245 dF

100

 

RA.L.O

RAT lo alert limit/occ

–40-245 dF

60

 

RA.H.O

RAT hi alert limit/occ

–40-245 dF

90

 

RA.L.U

RAT lo alert limit/unocc

–40-245 dF

40

 

RA.H.U

RAT hi alert limit/unocc

–40-245 dF

100

 

R.RH.L

RARH low alert limit

0-100 %

0

 

R.RH.H

RARH high alert limit

0-100 %

100

 

SP.L

SP low alert limit

0-5 "H2O

0

 

SP.H

SP high alert limit

0-5 "H2O

2

 

BP.L

BP lo alert limit

–0.25-0.25 "H2O

-0.25

 

BP.H

BP high alert limit

–0.25-0.25 "H2O

0.25

 

IAQ.H

IAQ high alert limit

0-5000

1200

 

TRIM

SENSOR TRIM CONFIG.

 

 

 

SAT.T

Air Temp Lvg SF Trim

–10 - 10 ^F

0

 

RAT.T

RAT Trim

–10 - 10 ^F

0

 

OAT.T

OAT Trim

–10 - 10 ^F

0

 

SPT.T

SPT Trim

–10 - 10 ^F

0

 

CTA.T

Cir A Sat.Cond.Temp Trim

–30 - 30 ^F

0

 

CTB.T

Cir B Sat.Cond.Temp Trim

–30 - 30 ^F

0

 

SP.A.T

Suct.Press.Circ.A Trim

–50 - 50 PSIG

0

 

SP.B.T

Suct.Press.Circ.B Trim

–50 - 50 PSIG

0

 

DP.A.T

Dis.Press.Circ.A Trim

–50 - 50 PSIG

0

 

DP.B.T

Dis.Press.Circ.B Trim

–50 - 50 PSIG

0

 

CL-4

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINECUT ALONG DOTTED LINE