out a LOW COOL or a HIGH COOL mode and maintain a low or high cool supply air set point.

C.TYP = 6 (SPT-2 STG)

This configuration will force the control to monitor the space temperature sensor to make a determination of mode and allow two stages of cooling.

MACHINE DEPENDENT CONFIGURATIONS — Some configurations are linked to the physical unit and must not be changed. The configurations are provided in case a field re- placement of a board occurs and the settings are not preserved by the download process of the new software. The following configurations apply to all machine control types (C.TYP) ex- cept 4 and 6. These configurations are located at the local dis- play under ConfigurationUNIT. See Table 44.

Table 44 — Machine Dependent Configurations

ITEM

EXPANSION

RANGE

CCN

DEFAULTS

POINT

 

 

 

 

UNIT

UNIT CONFIGURATION

 

 

SIZE

Unit Size (20-60)

20-60

UNITSIZE

*

RFG.T

REFRIG

0-1

REFRIG_T

*

CND.T

CND HX TYP

0-1

COILTYPE

*

*Dependent on unit.

Unit Size (SIZE) — There are several unit sizes (tons) for the A Series control. Make sure this configuration matches the size called out by the model number of the unit. This is important as the cooling stage tables are directly determined based on this configuration.

Refrigerant Type (RFG.T) — This configuration specifies the type of refrigerant used in the unit. Configuration RFG.T is set to 0 if the refrigerant used is R-22. Configuration RFG.T is set to 1 if the refrigerant used is R-410A. Make sure this configu- ration matches the refrigerant called out by the model number of the unit.

Condenser Type (CND.T) — This configuration specifies the type of condenser installed in the unit. Configuration CND.T is set to 0 if the condenser is a round tube, plate fin coil (RTPF). Configuration CND.T is set to 1 if the condenser is a micro- channel heat exchanger coil (MCHX). Make sure this configu- ration matches the condenser type called out by the model number of the unit.

SET POINTS — The set points for both cooling and heating are located at the local display under Setpoints. See Table 45.

SUPPLY AIR RESET CONFIGURATION — Supply Air Reset can be used to modify the current cooling supply air set point. Supply Air Reset is applicable to control types, C.TYP = 1,2,3, and 5. The configurations for reset can be found at the local display under ConfigurationEDT.R. See Table 46.

EDT Reset Configuration (RS.CF) — This configuration ap- plies to several machine control types (ConfigurationUNITC.TYP = 1,2,3, and 5).

0 = NO RESET

No supply air reset is in effect

1 = SPT RESET

Space temperature will be used as the reset control variable along with both RTIO and LIMT in the calculation of the final amount of reset to be applied (InputsRSET

SA.S.R).

2 = RAT RESET

Return-air temperature will be used as the reset control vari- able along with both RTIO and LIMT in the calculation of the final amount of reset to be applied (InputsRSETSA.S.R).

3 = 3RD PARTY RESET

The reset value is determined by a 4 to 20 mA third party input. An input of 4 mA would correspond to 0º F reset. An input of 20 mA would correspond to 20º F reset. Configur- ing the control for this option will cause RES.S to become enabled automatically with the CEM board. To avoid alarms make sure the CEM board and third party input are connected first before enabling this option.

Reset Ratio (RTIO) — This configuration is used when RS.CF is set to 1 or 2. For every degree that the controlling temperature (space/return) falls below the occupied cooling set point (OCSP), the calculated value of the supply air reset will rise by the number of degrees as specified by this parameter.

Reset Limit (LIMT) — This configuration is used when RS.CF is set to 1 or 2. This configuration places a clamp on the amount of supply air reset that can be applied.

EDT 4-20 mA Reset Input (RES.S) — This configuration is automatically enabled when ConfigurationEDT.RRS.CF is set to 3 (third party reset).

COOLING CONFIGURATION — Relevant configurations for mechanical cooling are located at the local display under ConfigurationCOOL. See Table 47.

Table 45 — Setpoints

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

OHSP

Occupied Heat Setpoint

40-99

dF

OHSP

68

OCSP

Occupied Cool Setpoint

40-99

dF

OCSP

75

UHSP

Unoccupied Heat Setpoint

40-99

dF

UHSP

55

UCSP

Unoccupied Cool Setpoint

40-99

dF

UCSP

90

GAP

Heat-Cool Setpoint Gap

2-10

^F

HCSP_GAP

5

V.C.ON

VAV Occ. Cool On Delta

0-25

^F

VAVOCON

3.5

V.C.OF

VAV Occ. Cool Off Delta

1-25

^F

VAVOCOFF

2

SASP

Supply Air Setpoint

45-75

dF

SASP

55

SA.HI

Supply Air Setpoint Hi

45-75

dF

SASP_HI

55

SA.LO

Supply Air Setpoint Lo

45-75

dF

SASP_LO

60

SA.HT

Heating Supply Air Setpt

90-145

dF

SASPHEAT

85

T.PRG

Tempering Purge SASP

–20-80

dF

TEMPPURG

50

T.CL

Tempering in Cool SASP

5-75

dF

TEMPCOOL

5

T.V.OC

Tempering Vent Occ SASP

–20-80

dF

TEMPVOCC

65

T.V.UN

Tempering Vent Unocc. SASP

–20-80

dF

TEMPVUNC

50

Table 46 — Supply Air Reset Configuration

ITEM

EXPANSION

 

RANGE

UNITS

CCN POINT

DEFAULT

EDT.R

EVAP.DISCHRGE TEMP RESET

 

 

 

 

 

RS.CF

EDT Reset Configuration

0

- 3

 

EDRSTCFG

0

RTIO

Reset Ratio

0

- 10

 

RTIO

2

LIMT

Reset Limit

0 - 20

^F

LIMT

10

RES.S

EDT 4-20 ma Reset Input

Enable/Disable

 

EDTRSENS

Disable

38

Page 38
Image 38
Carrier 48/50AJ specifications Machine Dependent Configurations, Setpoints, Supply Air Reset Configuration