Carrier 48/50AJ specifications Appendix A — Local Display Tables, Mode — Run Status

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 140
Image 140

APPENDIX A — LOCAL DISPLAY TABLES

MODE — RUN STATUS

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

WRITE STATUS

PAGE NO.

VIEW

AUTO VIEW OF RUN STATUS

 

 

 

 

 

HVAC

ascii string spelling out the hvac modes

 

 

string

 

90,91

OCC

Occupied ?

YES/NO

 

OCCUPIED

forcible

90,91

MAT

Mixed Air Temperature

 

dF

MAT

 

90,91

EDT

Evaporator Discharge Tmp

 

dF

EDT

 

90,91

LAT

Leaving Air Temperature

 

dF

LAT

 

90,91

EC.C.P

Economizer Control Point

 

dF

ECONCPNT

 

50,63,70,90,91

ECN.P

Economizer Act.Curr.Pos.

0-100

%

ECONOPOS

 

90,91

CL.C.P

Cooling Control Point

 

dF

COOLCPNT

 

41,42,63,90,91

C.CAP

Current Running Capacity

 

 

CAPTOTAL

 

90,91

HT.C.P

Heating Control Point

 

dF

HEATCPNT

 

53,90,91

HT.ST

Requested Heat Stage

 

 

HT_STAGE

 

54-56,90,91

H.MAX

Maximum Heat Stages

 

 

HTMAXSTG

 

54,90,91

ECON

ECONOMIZER RUN STATUS

 

 

 

 

 

ECN.P

Economizer Act.Curr.Pos.

0-100

%

ECONOPOS

 

50,64,91

ECN.C

Economizer Act.Cmd.Pos.

0-100

%

ECONOCMD

forcible

64,91

ACTV

Economizer Active ?

YES/NO

 

ECACTIVE

 

42,50,64,91

DISA

ECON DISABLING CONDITIONS

 

 

 

 

64,91

DISAUNAV

Econ Act. Unavailable?

YES/NO

 

ECONUNAV

 

64,91

DISAR.EC.D

Remote Econ. Disabled ?

YES/NO

 

ECONDISA

 

64,91

DISADBC

DBC - OAT Lockout?

YES/NO

 

DBC_STAT

 

64,91

DISADEW

DEW - OA Dewpt.Lockout?

YES/NO

 

DEW_STAT

 

64,91

DISADDBC

DDBD- OAT > RAT Lockout?

YES/NO

 

DDBCSTAT

 

64,91

DISAOAEC

OAEC- OA Enth Lockout?

YES/NO

 

OAECSTAT

 

64,91

DISADEC

DEC - Diff.Enth.Lockout?

YES/NO

 

DEC_STAT

 

64,91

DISAEDT

EDT Sensor Bad?

YES/NO

 

EDT_STAT

 

64,91

DISAOAT

OAT Sensor Bad ?

YES/NO

 

OAT_STAT

 

64,91

DISAFORC

Economizer Forced ?

YES/NO

 

ECONFORC

 

64,91

DISASFON

Supply Fan Not On 30s ?

YES/NO

 

SFONSTAT

 

64,91

DISACLOF

Cool Mode Not In Effect?

YES/NO

 

COOL_OFF

 

64,91

DISAOAQL

OAQ Lockout in Effect ?

YES/NO

 

OAQLOCKD

 

64,91

DISAHELD

Econ Recovery Hold Off?

YES/NO

 

ECONHELD

 

64,91

DISADH.DS

Dehumid. Disabled Econ?

YES/NO

 

DHDISABL

 

64,91

O.AIR

OUTSIDE AIR INFORMATION

 

 

 

 

64,91

O.AIROAT

Outside Air Temperature

 

dF

OAT

forcible

64,91

O.AIROA.RH

Outside Air Rel. Humidity

 

%

OARH

forcible

64,91

O.AIROA.E

Outside Air Enthalpy

 

 

OAE

 

64,91

O.AIROA.D.T

OutsideAir Dewpoint Temp

 

dF

OADEWTMP

 

64,91

COOL

COOLING INFORMATION

 

 

 

 

 

C.CAP

Current Running Capacity

 

%

CAPTOTAL

 

46,47,49,90,92

CUR.S

Current Cool Stage

 

 

COOL_STG

 

46,47,63,90,92

REQ.S

Requested Cool Stage

 

 

CL_STAGE

 

46,47,90,92

MAX.S

Maximum Cool Stages

 

 

CLMAXSTG

 

46,47,90,92

DEM.L

Active Demand Limit

 

 

DEM_LIM

forcible

46-48,90,92

SUMZ

COOL CAP. STAGE CONTROL

 

 

 

 

46,47,90,92

SUMZSMZ

Capacity Load Factor

 

%

SMZ

 

46,47,90,92

SUMZADD.R

Next Stage EDT Decrease

 

^F

ADDRISE

 

43,46,47,90,92

SUMZSUB.R

Next Stage EDT Increase

 

^F

SUBRISE

 

46,47,90,92

SUMZR.PCT

Rise Per Percent Capacity

 

 

RISE_PCT

 

46,47,90,92

SUMZY.MIN

Cap Deadband Subtracting

 

 

Y_MINUS

 

46,47,90,92

SUMZY.PLU

Cap Deadband Adding

 

 

Y_PLUS

 

46,47,90,92

SUMZZ.MIN

Cap Threshold Subtracting

 

 

Z_MINUS

 

46,47,91,92

SUMZZ.PLU

Cap Threshold Adding

 

 

Z_PLUS

 

46,47,91,92

SUMZH.TMP

High Temp Cap Override

 

 

HI_TEMP

 

46,47,91,92

SUMZL.TMP

Low Temp Cap Override

 

 

LOW_TEMP

 

46,47,91,92

SUMZPULL

Pull Down Cap Override

 

 

PULLDOWN

 

46,47,91,92

SUMZSLOW

Slow Change Cap Override

 

 

SLO_CHNG

 

47,91,92

TRIP

MODE TRIP HELPER

 

 

 

 

 

UN.C.S

Unoccup. Cool Mode Start

 

 

UCCLSTRT

 

46,53,92

UN.C.E

Unoccup. Cool Mode End

 

 

UCCL_END

 

46,53,92

OC.C.S

Occupied Cool Mode Start

 

 

OCCLSTRT

 

46,53,92

OC.C.E

Occupied Cool Mode End

 

 

OCCL_END

 

46,53,92

TEMP

Ctl.Temp RAT,SPT or Zone

 

 

CTRLTEMP

 

46,53,92

OC.H.E

Occupied Heat Mode End

 

 

OCHT_END

 

46,53,92

OC.H.S

Occupied Heat Mode Start

 

 

OCHTSTRT

 

46,53,92

UN.H.E

Unoccup. Heat Mode End

 

 

UCHT_END

 

46,53,92

UN.H.S

Unoccup. Heat Mode Start

 

 

UCHTSTRT

 

46,53,92

HVAC

ascii string spelling out the hvac modes

 

 

string

 

46,53,92

LINK

CCN - LINKAGE

 

 

 

 

 

MODE

Linkage Active - CCN

ON/OFF

 

MODELINK

 

92

L.Z.T

Linkage Zone Control Tmp

 

dF

LZT

 

92

L.C.SP

Linkage Curr. Cool Setpt

 

dF

LCSP

 

92

L.H.SP

Linkage Curr. Heat Setpt

 

dF

LHSP

 

92

HRS

COMPRESSOR RUN HOURS

 

 

 

 

 

HR.A1

Compressor A1 Run Hours

0-999999

HRS

HR_A1

config

92

HR.A2

Compressor A2 Run Hours

0-999999

HRS

HR_A2

config

92

HR.B1

Compressor B1 Run Hours

0-999999

HRS

HR_B1

config

92

HR.B2

Compressor B2 Run Hours

0-999999

HRS

HR_B2

config

92

STRT

COMPRESSOR STARTS

 

 

 

 

 

ST.A1

Compressor A1 Starts

0-999999

 

CY_A1

config

92

ST.A2

Compressor A2 Starts

0-999999

 

CY_A2

config

92

ST.B1

Compressor B1 Starts

0-999999

 

CY_B1

config

92

ST.B2

Compressor B2 Starts

0-999999

 

CY_B2

config

92

140

Page 140
Image 140
Carrier 48/50AJ specifications Appendix A — Local Display Tables, Mode — Run Status