Carrier 48/50AJ specifications CL-2

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 186
Image 186

ITEM

EXPANSION

 

RANGE

DEFAULT

ENTRY

HEAT

HEATING CONFIGURATION

 

 

 

 

HT.CF

Heating Control Type

0

- 4

0

 

HT.SP

Heating Supply Air Setpt

80 - 120 dF

85

 

OC.EN

Occupied Heating Enabled

Yes/No

No

 

LAT.M

MBB Sensor Heat Relocate

Yes/No

No

 

G.FOD

Fan-Off Delay, Gas Heat

45-600

45

 

E.FOD

Fan-Off Delay, Elec Heat

10-600

30

 

SG.CF

STAGED GAS CONFIGS

 

 

 

 

SG.CFHT.ST

Staged Gas Heat Type

0

- 4

0

 

SG.CFCAP.M

Max Cap Change per Cycle

5

- 45

45

 

SG.CFM.R.DB

S.Gas DB min.dF/PID Rate

0

- 5

0.5

 

SG.CFS.G.DB

St.Gas Temp. Dead Band

0

- 5 ^F

2

 

SG.CFRISE

Heat Rise dF/sec Clamp

0.05 - 0.2

0.06

 

SG.CFLAT.L

LAT Limit Config

0

- 20 ^F

10

 

SG.CFLIM.M

Limit Switch Monitoring?

Yes/No

No

 

SG.CFSW.H.T

Limit Switch High Temp

110 - 180 dF

170

 

SG.CFSW.L.T

Limit Switch Low Temp

100 - 170 dF

160

 

SG.CFHT.P

Heat Control Prop. Gain

0

- 1.5

1

 

SG.CFHT.D

Heat Control Derv. Gain

0

- 1.5

1

 

SG.CFHT.TM

Heat PID Rate Config

60 - 300 sec

90

 

SP

SUPPLY STATIC PRESS.CFG.

 

 

 

 

SP.CF

Static Pressure Config

0

- 1 (multi-text strings)

No

 

SP.FN

Static Pres.Fan Control?

Yes

Yes

 

SP.S

Static Pressure Sensor

Enable/Disable

Disable

 

SP.LO

Static Press. Low Range

-10 - 0

0

 

SP.HI

Static Press. High Range

0

- 10

5

 

SP.SP

Static Pressure Setpoint

0

- 5 "H2O

1.5

 

SP.MN

VFD Minimum Speed

0

- 100 %

20

 

SP.MX

VFD Maximum Speed

0

- 100 %

100

 

SP.FS

VFD Fire Speed Override

0

- 100 %

100

 

SP.RS

Stat. Pres. Reset Config

0

- 4 (multi-text strings)

0

 

SP.RT

SP Reset Ratio (/dF)

0

- 2.00 in. wg/dF

0.2

 

SP.LM

SP Reset Limit in iwc ()

0

- 2.00 in. wg

0.75

 

SP.EC

SP Reset Econo. Position

0

- 100 %

5

 

S.PID

STAT.PRESS.PID CONFIGS

 

 

 

 

S.PIDSP.TM

Stat.Pres.PID Run Rate

1

- 200 sec

2

 

S.PIDSP.P

Static Press. Prop. Gain

0

- 100

20

 

S.PIDSP.I

Static Pressure Intg. Gain

0

- 50

2

 

S.PIDSP.D

Static Pressure Derv. Gain

0

- 50

0

 

S.PIDSP.SG

Static Press.System Gain

0

- 50

1

 

ECON

ECONOMIZER CONFIGURATION

 

 

 

 

EC.EN

Economizer Installed?

Yes/No

Yes

 

EC.MN

Economizer Min.Position

0

- 100 %

5

 

EC.MX

Economizer Max.Position

0

- 100 %

98

 

E.TRM

Economzr Trim For SumZ ?

Yes/No

Yes

 

E.SEL

Econ ChangeOver Select

0

- 3 (multi-text strings)

1

 

OA.E.C

OA Enthalpy ChgOvr Selct

1

- 5 (multi-text strings)

4

 

OA.EN

Outdr.Enth Compare Value

18 - 28

24

 

OAT.L

High OAT Lockout Temp

–40 - 120 dF

60

 

O.DEW

OA Dewpoint Temp Limit

50 - 62 dF

55

 

ORH.S

Outside Air RH Sensor

Enable/Disable

Disable

 

E.TYP

Economizer Control Type

1-3 (multi-text strings)

1

 

EC.SW

Economizer Switch Config

0

- 2 (multi-text strings)

0

 

E.CFG

ECON.OPERATION CONFIGS

 

 

 

 

E.CFGE.P.GN

Economizer Prop.Gain

0.7 - 3.0

1

 

E.CFGE.RNG

Economizer Range Adjust

0.5 - 5.0 ^F

2.5

 

E.CFGE.SPD

Economizer Speed Adjust

0.1 - 10.0

0.75

 

E.CFGE.DBD

Economizer Deadband

0.1 - 2.0 ^F

0.5

 

UEFC

UNOCC.ECON.FREE COOLING

 

 

 

 

UEFCFC.CF

Unoc Econ Free Cool Cfg

0-2 (multi-text strings)

0

 

UEFCFC.TM

Unoc Econ Free Cool Time

0

- 720 min

120

 

UEFCFC.L.O

Un.Ec.Free Cool OAT Lock

40 - 70 dF

50

 

CL-2

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINECUT ALONG DOTTED LINE