ITEM

 

EXPANSION

 

RANGE

DEFAULT

ENTRY

BP

BUILDING PRESS. CONFIG

 

 

 

 

BP.CF

Building Press. Config

0-2

0

 

BP.RT

Bldg.Pres.PID Run Rate

5-120 sec

10

 

BP.P

Bldg. Press. Prop. Gain

0-5

0.5

 

BP.I

Bldg.Press.Integ.Gain

0-2

0.5

 

BP.D

Bldg.Press.Deriv.Gain

0-5

0.3

 

BP.SO

BP Setpoint Offset

0.0 - 0.5 “H2O

0.05

 

BP.MN

BP VFD Minimum Speed

0-100%

10

 

BP.MX

BP VFD Maximum Speed

0-100%

100

 

BP.FS

VFD/Act. Fire Speed/Pos.

0-100%

100

 

BP.MT

Power Exhaust Motors

1-2

1

 

BP.S

Building Pressure Sensor

Enable/Dsable

Dsable

 

BP.R

Bldg Press (+/-) Range

0

- 1.00 “H2O

0.25

 

BP.SP

Building Pressure Setp.

–0.25 0.25 "H2O

0.05

 

BP.P1

Power Exhaust On Setp.1

0

- 100 %

35

 

BP.P2

Power Exhaust On Setp.2

0

- 100 %

75

 

B.CFG

BP ALGORITHM CONFIGS

 

 

 

 

B.CFGBP.SL

Modulating PE Alg. Slct.

1-3

1

 

B.CFGBP.TM

BP PID Evaluation Time

0

- 10 min

1

 

B.CFGBP.ZG

BP Threshold Adjustment

0.1 - 10.0 “H2O

1

 

B.CFGBP.HP

High BP Level

0

- 1.000 “H2O

0.05

 

B.CFGBP.LP

Low BP Level

0

- 1.000 “H2O

0.04

 

D.LV.T

COOL/HEAT SETPT. OFFSETS

 

 

 

 

L.H.ON

Dmd Level

Lo Heat On

–1 - 2 ^F

1.5

 

H.H.ON

Dmd Level(+) Hi Heat On

0.5 - 20.0 ^F

0.5

 

L.H.OF

Dmd Level(-) Lo Heat Off

0.5 - 2 ^F

1

 

L.C.ON

Dmd Level

Lo Cool On

–1 - 2 ^F

1.5

 

H.C.ON

Dmd Level(+) Hi Cool On

0.5 - 20.0 ^F

0.5

 

L.C.OF

Dmd Level(-) Lo Cool Off

0.5 - 2 ^F

1

 

C.T.LV

Cool Trend Demand Level

0.1 - 5 ^F

0.1

 

H.T.LV

Heat Trend Demand Level

0.1 - 5 ^F

0.1

 

C.T.TM

Cool Trend Time

30 - 600 sec

120

 

H.T.TM

Heat Trend Time

30 - 600 sec

120

 

DMD.L

DEMAND LIMIT CONFIG.

 

 

 

 

DM.L.S

Demand Limit Select

0

- 3 (multi-text strings)

0

 

D.L.20

Demand Limit at 20 ma

0

- 100 %

100

 

SH.NM

Loadshed Group Number

0

- 99

0

 

SH.DL

Loadshed Demand Delta

0

- 60 %

0

 

SH.TM

Maximum Loadshed Time

0

- 120 min

60

 

D.L.S1

Demand Limit Sw.1 Setpt.

0

- 100 %

80

 

D.L.S2

Demand Limit Sw.2 Setpt.

0

- 100 %

50

 

IAQ

INDOOR AIR QUALITY CFG.

 

 

 

 

DCV.C

DCV ECONOMIZER SETPOINTS

 

 

 

 

DCV.CEC.MN

Economizer Min.Position

0

- 100 %

5

 

DCV.CIAQ.M

IAQ Demand Vent Min.Pos.

0

- 100 %

0

 

AQ.CF

AIR QUALITY CONFIGS

 

 

 

 

AQ.CFIQ.A.C

IAQ Analog Sensor Config

0

- 4 (multi-text strings)

0

 

AQ.CFIQ.A.F

IAQ 4-20 ma Fan Config

0

- 2 (multi-text strings)

0

 

AQ.CFIQ.I.C

IAQ Discrete Input Config

0

- 2 (multi-text strings)

0

 

AQ.CFIQ.I.F

IAQ Disc.In. Fan Config

0

- 2 (multi-text strings)

0

 

AQ.CFOQ.A.C

OAQ 4-20ma Sensor Config

0

- 2 (multi-text strings)

0

 

AQ.SP

AIR QUALITY SETPOINTS

 

 

 

 

AQ.SPIQ.O.P

IAQ Econ Override Pos.

0

- 100 %

100

 

AQ.SPDAQ.L

Diff.Air Quality LoLimit

0

- 1000

100

 

AQ.SPDAQ.H

Diff.Air Quality HiLimit

100 - 2000

700

 

AQ.SPD.F.OF

DAQ PPM Fan Off Setpoint

0

- 2000

200

 

AQ.SPD.F.ON

DAQ PPM Fan On Setpoint

0

- 2000

400

 

AQ.SPIAQ.R

Diff. AQ Responsiveness

–5 - 5

0

 

AQ.SPOAQ.L

OAQ Lockout Value

0

- 2000

0

 

AQ.SPOAQ.U

User Determined OAQ

0

- 5000

400

 

AQ.S.R

AIR QUALITY SENSOR RANGE

 

 

 

 

CL-3

Page 187
Image 187