Table 114 — Alert and Alarm Codes (cont)

ALARM

 

 

 

 

 

 

 

 

OR

 

DESCRIPTION

 

ACTION TAKEN BY CONTROL

RESET

PROBABLE CAUSE

ALERT

 

 

METHOD

 

 

 

 

 

 

 

NUMBER

 

 

 

 

 

 

 

T300

 

Space Temperature Below Limit

 

 

Stop cooling, but continue

Automatic

Outdoor dampers stuck, no load

 

 

 

to heat

 

 

 

 

 

 

 

 

 

T301

 

Space Temperature Above Limit

 

 

Stop heating, but continue

Automatic

High load, dampers open

 

 

 

to cool

 

 

 

 

 

 

 

 

 

T302

 

Supply Temperature Below Limit

 

 

Continue to run unit

Automatic

Dampers open, check configuration

 

 

 

setpoint

 

 

 

 

 

 

 

 

 

T303

 

Supply Temperature Above Limit

 

 

Continue to run unit

Automatic

Dampers open, check configuration

 

 

 

setpoint

 

 

 

 

 

 

 

 

 

T304

 

Return Temperature Below Limit

 

 

Continue to run unit

Automatic

Dampers open, check configuration

 

 

 

setpoint

 

 

 

 

 

 

 

 

 

T305

 

Return Temperature Above Limit

 

 

Continue to run unit

Automatic

Dampers open, check configuration

 

 

 

setpoint

 

 

 

 

 

 

 

 

 

T308

 

Return Air Relative Humidity Below Limit

Alert

Automatic

Configuration error, or sensor error

T309

 

Return Air Relative Humidity Above Limit

Continue to run unit

Automatic

Dampers open, check configuration

 

setpoint

 

 

 

 

 

 

 

 

 

T310

 

Supply Duct Static Pressure Below Limit

Continue to run unit

Automatic

VFD problem, broken fan belt

T311

 

Supply Duct Static Pressure Above Limit

Continue to run unit

Automatic

VFD problem, broken fan belt

T312

 

Building Static Pressure Below Limit

 

Continue to run unit

Automatic

Exhaust issues, check setpoint

T313

 

Building Static Pressure Above Limit

 

Continue to run unit

Automatic

Exhaust issues, check setpoint

T314

 

IAQ Above Limit

 

 

 

Continue to run unit

Automatic

Damper or IAQ control issues

A404

 

Fire Shut Down Emergency Mode (fire-smoke)

Unit Shutdown

Automatic

Smoke detector switch or external

 

switch

 

 

 

 

 

 

 

 

 

A405

 

Evacuation Emergency Mode

 

 

Run power exhaust

Automatic

Special fire mode control

A406

 

Pressurization Emergency Mode

 

 

Run supply fan

Automatic

Special fire mode control

A407

 

Smoke Purge Emergency Mode

 

 

Run supply and exhaust fans

Automatic

Special fire mode control

T408

 

Dirty Air Filter

 

 

 

Continue to run unit

Automatic

Dirty filter, switch setting

A409

 

Supply Fan Status Failure

 

 

 

Stop unit

Automatic

Fan drive failure

T409

 

Supply Fan Status Failure

 

 

 

Continue to run unit

Automatic

Fan drive failure, or sensor failure

T414

 

Loss of Communication with the Belimo Actuator

Close economizer

Automatic

Calibrate economizer, economizer

 

failure, wiring

 

 

 

 

 

 

 

 

 

T414

 

Belimo Actuator Direction Error

 

 

Close economizer

Automatic

Motor direction switch wrong, wiring

T414

 

Belimo Actuator Failure

 

 

 

Attempt to close economizer

Automatic

Motor failure

T414

 

Belimo Actuator Jammed

 

 

 

Close economizer

Automatic

Obstruction in damper

T414

 

Belimo Actuator Range Error

 

 

Close economizer

Automatic

Calibrate economizer

T420

 

R-W1 Jumper Must Be Installed to Run Heat in Service

No heat

Automatic

Add red wire jumpers

 

Test

 

 

 

 

 

 

 

 

 

 

 

 

T421

 

Thermostat Y2 Input ON without Y1 ON

Assume Y2 is Y1

Automatic

Thermostat wiring error

T422

 

Thermostat W2 Input ON without W1 ON

Assume W2 is W1

Automatic

Thermostat wiring error

T423

 

Thermostat Y and W Inputs ON

 

 

Alert

Automatic

Thermostat issues

T424

 

Thermostat G Input OFF on a Call for Cooling

Turn fan on

Automatic

Thermostat or wiring issues

T500

 

Current Sensor Board Failure - A1

 

 

Stop compressor A1

Automatic

Faulty board or wiring

T501

 

Current Sensor Board Failure - A2

 

 

Stop compressor A2

Automatic

Faulty board or wiring

T502

 

Current Sensor Board Failure - B1

 

 

Stop compressor B1

Automatic

Faulty board or wiring

T503

 

Current Sensor Board Failure - B2

 

 

Stop compressor B2

Automatic

Faulty board or wiring

A700

 

Supply Air Temperature Sensor Failure

 

Stop staged gas heat

Automatic

Faulty sensor or wiring error

T701

 

Staged Gas Thermistor 1 Failure

 

 

Stop staged gas heat

Automatic

Faulty sensor or wiring error

T702

 

Staged Gas Thermistor 2 Failure

 

 

Stop staged gas heat

Automatic

Faulty sensor or wiring error

T703

 

Staged Gas Thermistor 3 Failure

 

 

Stop staged gas heat

Automatic

Faulty sensor or wiring error

A704

 

Staged Gas Leaving Air Temp Sum Total Failure

Stop staged gas heat

Automatic

Faulty sensor or wiring error

T705

 

Limit Switch Thermistor Failure

 

 

Stop staged gas heat

Automatic

Faulty switch or wiring

 

 

 

LEGEND

 

 

 

 

 

 

Axxx —

Alarm

Pxxx —

Pre-Alert

 

 

 

CEM

Controls Expansion module

Txxx

Alert

 

 

 

IAQ

Indoor Air Quality

TXV

Thermostatic Expansion Valve

 

 

OAT

Outdoor Air Temperature

VFD

Variable Frequency Drive

 

 

For 48/50A2,A3,A4,A5 units:

Compressor internal overload protector is open. Internal overload protectors are used in the Copeland compressors in all units except size 60 ton units with voltages of 208/230-v, 380-v, and 575-v.

Compressor external overload protector (Kriwan module) has activated. The Copeland compressors in size 60 ton units with voltages of 208/230-v, 380-v, and 575-v use external overload protector modules that are mounted in the compressor wiring junction box. Temperature sensors embedded in the compressor motor windings are the inputs to the module. The module is powered with 120 vac from the units main control box. The module output is a normally closed contact that is wired in series with the compressor contactor coil. In a compressor motor overload condition, the contact opens de-energizing the compressor contactor.

Circuit breaker trip. The compressors are protected from short circuit by a breaker in the control box. On the 020-050

size units there is one breaker per two compressors and on the 060 size units there is one breaker per compressor.

Wiring Error. A wiring error might not allow the compres- sor to start.

To check out alerts 051, 052, 055 and 056:

1.Turn on the compressor in question using Service Test mode. If the compressor does not start, then most likely the problem is one of the following: HPS open, open internal protection, circuit breaker trip, incorrect safety wiring, or incorrect compressor wiring.

2.If the compressor does start verify it is rotating in the correct direction.

IMPORTANT: Prolonged operation in the wrong direction can damage the compressor. Correct rotation can be veri- fied by a gage set and looking for a differential pressure rise on start-up.

95

Page 95
Image 95
Carrier 48/50AJ specifications Cem