Carrier 48/50AJ specifications Alert Limit Configuration, Sensor Trim Configuration

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 73
Image 73
Table 87 — Alert Limit Configuration

then Alert 309 will occur. The unit will continue to run and the alert will automatically reset.

Supply Duct Pressure Low Alert Limit (SP.L) — If the unit is a VAV unit with a supply duct pressure sensor and the mea- sured supply duct static pressure is below the configurable SP Low Alert Limit (DP.L), then Alert 310 will occur. The unit will continue to run and the alert will automatically reset.

Supply Duct Pressure High Alert Limit (SP.H) — If the unit is a VAV unit with a supply duct pressure sensor and the mea- sured supply duct static pressure is above the configurable SP High Alert Limit (SP.H), then Alert 311 will occur. The unit will continue to run and the alert will automatically reset.

Building Pressure Low Alert Limit (BP.L) — If the unit is configured to use modulating power exhaust then a building static pressure limit can be configured using the BP Low Alert Limit (BP.L). If the measured pressure is below the limit then Alert 312 will occur.

Building Pressure High Alert Limit (BP.H) — If the unit is configured to use modulating power exhaust then a building static pressure limit can be configured using the BP Hi Alert Limit (BP.H). If the measured pressure is above the limit, then Alert 313 will occur.

Indoor Air Quality High Alert Limit (IAQ.H) — If the unit is configured to use a CO2 sensor and the level is above the configurable IAQ High Alert Limit (IAQ.H) then the alert will occur. The unit will continue to run and the alert will automati- cally reset.

Sensor Trim Configuration — The TRIM submenu is used to calibrate the sensor trim settings. The trim settings are used when the actual measured reading does not match the sensor output. The sensor can be adjusted to match the actual measured reading with the trim function. A list is shown in Table 88.

IMPORTANT: Sensor trim must not be used to extend unit operation past the allowable operating range. Doing so may void the warranty.

Air Temperature Leaving Supply Fan Sensor (SAT.T) — This variable is used to adjust the supply fan temperature sensor reading. The sensor reading can be adjusted ± 10° F to match the actual measured temperature.

Return Air Temperature Sensor Trim (RAT.T) — This vari- able is used to adjust the return air temperature sensor reading. The sensor reading can be adjusted ± 10° F to match the actual measured temperature.

Outdoor Air Temperature Sensor Trim (OAT.T) — This vari- able is used to adjust the outdoor air temperature sensor read- ing. The sensor reading can be adjusted ± 10° F to match the actual measured temperature.

Space Temperature Sensor Trim (SPT.T) — This variable is used to adjust the space temperature sensor reading. The sensor reading can be adjusted ± 10° F to match the actual measured temperature.

Circuit A Saturated Condenser Temperature Trim (CTA.T) — This variable is used to adjust the saturated condenser tempera- ture sensor reading for circuit A. The sensor reading can be adjusted ± 30° F to match the actual measured temperature. Used on 48/50AJ,AK,AW,AY units only.

Circuit B Saturated Condenser Temperature Trim (CTB.T) — This variable is used to adjust the saturated condenser tempera- ture sensor reading for circuit B. The sensor reading can be adjusted ± 30° F to match the actual measured temperature. Used on 48/50AJ,AK,AW,AY units only.

Suction Pressure Circuit A Trim (SP.A.T) — This variable is used to adjust the suction pressure sensor reading for circuit A. The sensor reading can be adjusted ± 50 psig to match the actu- al measured pressure.

Suction Pressure Circuit B Trim (SP.B.T) — This variable is used to adjust the suction pressure sensor reading for circuit B. The sensor reading can be adjusted ± 50 psig to match the actu- al measured pressure.

Table 87 — Alert Limit Configuration

ITEM

EXPANSION

RANGE

UNITS

POINT

DEFAULT

SP.L.O

SPT lo alert limit/occ

-10-245

dF

SPLO

60

SP.H.O

SPT hi alert limit/occ

-10-245

dF

SPHO

85

SP.L.U

SPT lo alert limit/unocc

-10-245

dF

SPLU

45

SP.H.U

SPT hi alert limit/unocc

-10-245

dF

SPHU

100

SA.L.O

EDT lo alert limit/occ

-40-245

dF

SALO

40

SA.H.O

EDT hi alert limit/occ

-40-245

dF

SAHO

100

SA.L.U

EDT lo alert limit/unocc

-40-245

dF

SALU

40

SA.H.U

EDT hi alert limit/unocc

-40-245

dF

SAHU

100

RA.L.O

RAT lo alert limit/occ

-40-245

dF

RALO

60

RA.H.O

RAT hi alert limit/occ

-40-245

dF

RAHO

90

RA.L.U

RAT lo alert limit/unocc

-40-245

dF

RALU

40

RA.H.U

RAT hi alert limit/unocc

-40-245

dF

RAHU

100

R.RH.L

RARH low alert limit

0-100

%

RRHL

0

R.RH.H

RARH high alert limit

0-100

%

RRHH

100

SP.L

SP low alert limit

0-5

"H2O

SPL

0

SP.H

SP high alert limit

0-5

"H2O

SPH

2

BP.L

BP lo alert limit

-0.25-0.25

"H2O

BPL

-0.25

BP.H

BP high alert limit

-0.25-0.25

"H2O

BPH

0.25

IAQ.H

IAQ high alert limit

0-5000

 

IAQH

1200

Table 88 — Sensor Trim Configuration

ITEM

EXPANSION

RANGE

UNITS

POINT

DEFAULT

SAT.T

Air Temp Lvg SF Trim

-10 - 10

^F

SAT_TRIM

0

RAT.T

RAT Trim

-10 - 10

^F

RAT_TRIM

0

OAT.T

OAT Trim

-10 - 10

^F

OAT_TRIM

0

SPT.T

SPT Trim

-10 - 10

^F

SPT_TRIM

0

CTA.T

Cir A Sat. Cond. Temp Trim

-30 - 30

^F

SCTA_TRIM

0

CTB.T

Cir B Sat. Cond. Temp Trim

-30 - 30

^F

SCTB_TRIM

0

SP.A.T

Suct.Press.Circ.A Trim

-50 - 50

PSIG

SPA_TRIM

0

SP.B.T

Suct.Press.Circ.B Trim

-50 - 50

PSIG

SPB_TRIM

0

DP.A.T

Dis.Press.Circ.A Trim

-50 - 50

PSIG

DPA_TRIM

0

DP.B.T

Dis.Press.Circ.B Trim

-50 - 50

PSIG

DPB_TRIM

0

73

Page 73
Image 73
Carrier 48/50AJ specifications Alert Limit Configuration, Sensor Trim Configuration