APPENDIX B — CCN TABLES (cont)

STATUS DISPLAY TABLES (cont)

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

TEMPS

Air Temp Lvg Supply Fan

 

dF

SAT

 

 

 

 

 

Return Air Temperature

 

dF

RAT

forcible

 

Outside Air Temperature

 

dF

OAT

forcible

 

Space Temperature

 

dF

SPT

forcible

 

Space Temperature Offset

 

^F

SPTO

forcible

 

Staged Gas LAT Sum

 

dF

LAT_SGAS

 

 

Staged Gas LAT 1

 

dF

LAT1SGAS

 

 

Staged Gas LAT 2

 

dF

LAT2SGAS

 

 

Staged Gas LAT 3

 

dF

LAT23SGAS

 

 

Staged Gas Limit Sw.Temp

 

dF

LIMSWTMP

 

 

Cir A Sat.Condensing Tmp

 

dF

SCTA

 

 

Cir B Sat.Condensing Tmp

 

dF

SCTB

 

 

Cir A Sat.Suction Temp.

 

dF

SSTA

 

 

Cir B Sat.Suction Temp.

 

dF

SSTB

 

TSTAT

Control Mode………..:

ascii text strings

 

 

 

 

 

 

 

 

Thermostat Y1 Input

On/Off

 

Y1

forcible

 

Thermostat Y2 Input

On/Off

 

Y2

forcible

 

Thermostat W1 Input

On/Off

 

W1

forcible

 

Thermostat W2 Input

On/Off

 

W2

forcible

 

Thermostat G Input

On/Off

 

G

forcible

UINPUTS

Filter Status Input

Dirty/Clean

 

FLTS

forcible

 

 

 

Fan request from IGC

On/Off

 

IGCFAN

 

 

Fire Shutdown Switch

Alarm/Normal

 

FSD

forcible

 

Thermostat G Input

On/Off

 

G

forcible

 

Thermostat W2 Input

On/Off

 

W2

forcible

 

Thermostat W1 Input

On/Off

 

W1

forcible

 

Thermostat Y2 Input

On/Off

 

Y2

forcible

 

Thermostat Y1 Input

On/Off

 

Y1

forcible

 

Economizer Control Input

On/Off

 

ECOSW

forcible

 

Remote Economizer Enable

Yes/No

 

ECONENBL

forcible

 

Econo Position Override

Yes/No

 

ECOORIDE

forcible

 

Remote Input State

On/Off

 

RMTIN

forcible

 

Supply Fan Status Switch

On/Off

 

SFS

forcible

 

Demand Limit Switch 1

On/Off

 

DMD_SW1

forcible

 

Demand Limit Switch 2

On/Off

 

DMD_SW2

forcible

 

Pressurization Input

Alarm/Normal

 

PRES

forcible

 

Evacuation Input

Alarm/Normal

 

EVAC

forcible

 

Smoke Purge Input

Alarm/Normal

 

PURG

forcible

 

IAQ - Discrete Input

High/Low

 

IAQIN

forcible

 

Dehumidify Switch Input

On/Off

 

DHDISCIN

forcible

UOUTPUTS

FANS

 

 

 

 

 

 

 

 

 

 

Supply Fan Relay

On/Off

 

SFAN_RLY

 

 

Supply Fan VFD Speed

0-100

%

SFAN_VFD

 

 

Supply Fan Request

Yes/No

 

SFANFORC

forcible

 

Power Exhaust Relay A

On/Off

 

PE_A

 

 

Power Exhaust Relay B

On/Off

 

PE_B

 

 

Power Exhaust Relay C

On/Off

 

PE_C

 

 

Condenser Fan A

On/Off

 

CONDFANA

 

 

Condenser Fan B

On/Off

 

CONDFANB

 

 

COOLING

 

 

 

 

 

Compressor A1 Relay

On/Off

 

CMPA1

 

 

Compressor A2 Relay

On/Off

 

CMPA2

 

 

Minimum Load Valve

On/Off

 

MLV

 

 

Compressor B1 Relay

On/Off

 

CMPB1

 

 

Compressor B2 Relay

On/Off

 

CMPB2

 

 

HEATING

 

 

 

 

 

Heat Relay 1

On/Off

 

HS1

 

 

Heat Relay 2

On/Off

 

HS2

 

 

Relay 3 W1 Gas Valve 2

On/Off

 

HS3

 

 

Relay 4 W2 Gas Valve 2

On/Off

 

HS4

 

 

Relay 5 W1 Gas Valve 3

On/Off

 

HS5

 

 

Relay 6 W2 Gas Valve 3

On/Off

 

HS6

 

 

Heat Interlock Relay

On/Off

 

HIR

forcible

 

ECONOMIZER

 

 

 

 

 

Economizer Act.Curr.Pos.

0-100

%

ECONOPOS

 

 

Economizer Act.Cmd.Pos.

0-100

%

ECONOCMD

forcible

 

Economizer Power Relay

On/Off

 

ECON_PWR

forcible

 

GENERAL OUTPUTS

 

 

 

 

 

Remote Alarm/Aux Relay

On/Off

 

ALRM

forcible

150

Page 150
Image 150
Carrier 48/50AJ specifications 150, Display Name Range Units Point Name Write Status Temps, Tstat, Uinputs, Uoutputs