Carrier 48/50AJ specifications Appendix C - Vfd Information, Table A — VFD Terminal Designations

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 161
Image 161
APPENDIX C — VFD INFORMATION

APPENDIX C — VFD INFORMATION

On variable air volume units with optional VFD, the supply fan speed is controlled by a 3-phase VFD. The VFD is located in the supply fan section behind a removable panel. The VFD speed is controlled directly by the ComfortLink™ controls through a 4 to 20 mA signal based on a supply duct pressure sensor. The VFD has a display, which can be used for service diagnostics, but setup of the building pressure and control loop factors should be done through the scrolling marquee display. The VFD is powered during normal operation to prevent

condensation from forming on the boards during the off mode and is stopped by driving the speed to 0 (by sending a 4 mA signal to the VFD).

The A Series units use ABB VFDs. The interface wiring for the VFDs is shown in Fig. A. The VFD connects through an isolation board to the 4 to 20 mA RCB board. Terminal designations are shown in Table A. Configurations are shown in Table B.

Table A — VFD Terminal Designations

TERMINAL

FUNCTION

U1

 

V1

 

W1

Three-Phase Main Circuit Input Power Supply

U2

 

V2

Three-Phase AC Output to Motor, 0 V to

W2

Maximum Input Voltage Level

X1-11 (GND)

 

X1-12 (COMMON)

Factory-supplied jumper

X1-10 (24 VDC)

 

X1-13 (DI-1)

Run (factory-supplied jumper)

X1-10 (24 VDC)

Start Enable 1 (Factory-supplied jumper). When

X1-16 (DI-4)

opened the drive goes to emergency stop.

X1-2 (AI-1)

 

X1-3 (AGND)

Factory wired for 4 to 20 mA remote input

A48-7712

Fig. A — VFD Wiring

161

Page 161
Image 161
Carrier 48/50AJ specifications Appendix C - Vfd Information, Table A — VFD Terminal Designations, Fig. A — VFD Wiring