APPENDIX E — UPC OPEN CONTROLLER (cont)

NETWORK POINTS LIST (cont)

BACNET

POINT NAME

READ

UNITS

DEFAULT

RANGE

BACNET

UNIT

OBJECT ID

ONLY

VALUE

OBJECT NAME

POINT

 

 

 

 

 

 

 

 

 

 

 

AV:1009

IAQ - PPM Indoor CO2

W

n/a

n/a

0-5000

iaq_1

IAQ

 

 

 

 

 

 

 

 

AV:1016

Static Pressure

R

in H2O

n/a

n/a

static_press_1

SP

 

 

 

 

 

 

 

 

AV:1022

HVAC Mode Numerical Form

R

n/a

n/a

n/a

hvac_mode_1

MODEHVAC

 

 

 

 

 

 

 

 

AV:1023

Current Running Capacity

R

%

n/a

n/a

cool_capacity_1

CAPTOTAL

 

 

 

 

 

 

 

 

AV:1024

Cooling Control Point

R

°F

n/a

n/a

cool_ctrl_point_1

COOLCPNT

 

 

 

 

 

 

 

 

AV:1025

Heating Control Point

R

°F

n/a

n/a

heat_ctrl_point_1

HEATCPNT

 

 

 

 

 

 

 

 

AV:1027

Leaving Air Temperature

R

°F

n/a

n/a

lvg_air_temperature_1

LAT

 

 

 

 

 

 

 

 

AV:1028

Economizer Act. Curr. Pos

R

%

n/a

n/a

econ_pos_1

ECONOPOS

 

 

 

 

 

 

 

 

AV:1030

Controlling Return Temp

W

°F

n/a

-40-240

ra_temp_1

RETURN_T

 

 

 

 

 

 

 

 

AV:1070

Building Pressure

R

in H2O

n/a

n/a

bldg_static_press_1

BP

 

 

 

 

 

 

 

 

AV:1500

Mixed Air Temperature

R

°F

n/a

n/a

ma_temp_1

MAT

 

 

 

 

 

 

 

 

AV:1600

Cir A Suction Pressure

R

psig

n/a

n/a

suction_press_a_1

SP_A

 

 

 

 

 

 

 

 

AV:1601

Cir A Discharge Pressure

R

psig

n/a

n/a

discharge_press_a_1

DP_A

 

 

 

 

 

 

 

 

AV:1602

Cir A Sat. Condensing Temperature

R

°F

n/a

n/a

sat_cond_temp_a_1

SCTA

 

 

 

 

 

 

 

 

AV:1603

Cir A Sat. Suction Temperature

R

°F

n/a

n/a

sat_suction_temp_a_1

SSTA

 

 

 

 

 

 

 

 

AV:1604

Cir B Suction Pressure

R

psig

n/a

n/a

suction_press_b_1

SP_B

 

 

 

 

 

 

 

 

AV:1605

Cir B Discharge Pressure

R

psig

n/a

n/a

discharge_press_b_1

DP_B

 

 

 

 

 

 

 

 

AV:1606

Cir B Sat. Condensing Temperature

R

°F

n/a

n/a

sat_cond_temp_b_1

SCTB

 

 

 

 

 

 

 

 

AV:1607

Cir B Sat. Suction Temperature

R

°F

n/a

n/a

sat_suction_temp_b_1

SSTB

 

 

 

 

 

 

 

 

AV:2003

Requested Heat Stage

R

n/a

n/a

n/a

heat_run_1

HT_STAGE

 

 

 

 

 

 

 

 

AV:2007

Controlling Space Temp

W

°F

n/a

-40-240

space_temp_1

SPACE_T

 

 

 

 

 

 

 

 

AV:2050

Supply Fan VFD Speed

R

%

n/a

n/a

sfvfdtst_1

SFAN_VFD

 

 

 

 

 

 

 

 

AV:2075

Exhaust Fan VFD Speed

R

%

n/a

n/a

ef_vfd_output_1

EFAN_VFD

 

 

 

 

 

 

 

 

AV:2901

User Defined Analog 1

n/a

n/a

n/a

n/a

user_analog_1_1

n/a

 

 

 

 

 

 

 

 

AV:2902

User Defined Analog 2

n/a

n/a

n/a

n/a

user_analog_2_1

n/a

 

 

 

 

 

 

 

 

AV:2903

User Defined Analog 3

n/a

n/a

n/a

n/a

user_analog_3_1

n/a

 

 

 

 

 

 

 

 

AV:2904

User Defined Analog 4

n/a

n/a

n/a

n/a

user_analog_4_1

n/a

 

 

 

 

 

 

 

 

AV:2905

User Defined Analog 5

n/a

n/a

n/a

n/a

user_analog_5_1

n/a

 

 

 

 

 

 

 

 

AV:3001

Cooling Occupied Setpoint

W

°F

75

40-99

occ_cl_stpt_1

OCSP

 

 

 

 

 

 

 

 

AV:3002

Heating Occupied Setpoint

W

°F

68

409-99

occ_ht_stpt_1

OHSP

 

 

 

 

 

 

 

 

AV:3003

Cooling Unoccupied Setpoint

W

°F

90

40-99

unocc_cl_stpt_1

UCSP

 

 

 

 

 

 

 

 

AV:3004

Heating Unoccupied Setpoint

W

°F

55

40-99

unocc_ht_stpt_1

UHSP

 

 

 

 

 

 

 

 

AV:3007

Supply Air Setpoint

W

°F

55

45-75

sa_temp_stpt_1

SASP

 

 

 

 

 

 

 

 

AV:3016

IAQ Demand Vent Min.Pos.

W

%

0

0-100

iaq_min_pos_1

IAQMINP

 

 

 

 

 

 

 

 

AV:3050

Static Pressure Setpoint

W

in H2O

1.5

0-5

sa_static_stpt_1

SPSP

 

 

 

 

 

 

 

 

AV:3070

Building Pressure Setp.

W

in H2O

0.05

-0.25-

bldg_press_stpt_1

BPSP

0.25

 

 

 

 

 

 

 

AV:4005

Economizer Min.Position

W

%

5

0-100

econ_min_1

ECONOMIN

 

 

 

 

 

 

 

 

AV:9008

High OAT Lockout Temp

W

°F

60

-40-120

econ_oat_lockout_1

OAT_LOCK

 

 

 

 

 

 

 

 

See legend on page 182.

179

Page 179
Image 179