APPENDIX A — LOCAL DISPLAY TABLES (cont)

MODE — CONFIGURATION (cont)

ITEM

 

EXPANSION

 

RANGE

UNITS

CCN POINT

DEFAULT

PAGE NO.

BP

BUILDING PRESS. CONFIG

 

 

 

 

 

 

BP.CF

Building Press. Config

0-3

 

BLDG_CFG

0

29,64,65

BP.RT

Bldg.Pres.PID Run Rate

5-120

sec

BPIDRATE

10

64,65

BP.P

Bldg. Press. Prop. Gain

0-5

 

BLDGP_PG

0.5

64,65

BP.I

Bldg.Press.Integ.Gain

0-2

 

BLDGP_IG

0.5

64,65

BP.D

Bldg.Press.Deriv.Gain

0-5

 

BLDGP_DG

0.3

64,65

BP.SO

BP Setpoint Offset

0.0 - 0.5

“H2O

BPSO

0.05

64,65

BP.MN

BP VFD Minimum Speed

0-100

%

BLDGPMIN

10

64,65

BP.MX

BP VFD Maximum Speed

0-100

%

BLDGPMAX

100

64,65

BP.FS

VFD/Act. Fire Speed/Pos.

0-100

%

BLDGPFSO

100

64,65

BP.MT

Power Exhaust Motors

1-2

 

PWRM

1

64,65

BP.S

Building Pressure Sensor

Enable/Dsable

 

BPSENS

Dsable

64,65

BP.R

Bldg Press (+/-) Range

0

- 1.00

“H2O

BP_RANGE

0.25

64,65

BP.SP

Building Pressure Setp.

–0.25 -> 0.25

"H2O

BPSP

0.05

29,64,65

BP.P1

Power Exhaust On Setp.1

0

- 100

%

PES1

35

29,64,65

BP.P2

Power Exhaust On Setp.2

0

- 100

%

PES2

75

29,64,65

B.CFG

BP ALGORITHM CONFIGS

 

 

 

 

 

64,65

B.CFGBP.SL

Modulating PE Alg. Slct.

1-3

 

BPSELECT

1

64,65

B.CFGBP.TM

BP PID Evaluation Time

0

- 10

min

BPPERIOD

1

64,65

B.CFGBP.ZG

BP Threshold Adjustment

0.1 - 10.0

“H2O

BPZ_GAIN

1

64,65

B.CFGBP.HP

High BP Level

0

- 1.000

“H2O

BPHPLVL

0.05

64,65

B.CFGBP.LP

Low BP Level

0

- 1.000

“H2O

BPLPLVL

0.04

64-66

D.LV.T

COOL/HEAT SETPT. OFFSETS

 

 

 

 

 

 

L.H.ON

Dmd Level

Lo Heat On

–1 - 2

^F

DMDLHON

1.5

27,28,52

H.H.ON

Dmd Level(+) Hi Heat On

0.5 - 20.0

^F

DMDHHON

0.5

27,28,52

L.H.OF

Dmd Level(-) Lo Heat Off

0.5 - 2

^F

DMDLHOFF

1

27,28,52

L.C.ON

Dmd Level

Lo Cool On

–1 - 2

^F

DMDLCON

1.5

27,28,52

H.C.ON

Dmd Level(+) Hi Cool On

0.5 - 20.0

^F

DMDHCON

0.5

27,28,52

L.C.OF

Dmd Level(-) Lo Cool Off

0.5 - 2

^F

DMDLCOFF

1

27,28,52

C.T.LV

Cool Trend Demand Level

0.1 - 5

^F

CTRENDLV

0.1

52

H.T.LV

Heat Trend Demand Level

0.1 - 5

^F

HTRENDLV

0.1

52

C.T.TM

Cool Trend Time

30 - 600

sec

CTRENDTM

120

52

H.T.TM

Heat Trend Time

30 - 600

sec

HTRENDTM

120

52

DMD.L

DEMAND LIMIT CONFIG.

 

 

 

 

 

 

DM.L.S

Demand Limit Select

0

- 3 (multi-text strings)

 

DMD_CTRL

0

31,35,48,49,98

D.L.20

Demand Limit at 20 ma

0

- 100

%

DMT20MA

100

31,49

SH.NM

Loadshed Group Number

0

- 99

 

SHED_NUM

0

49

SH.DL

Loadshed Demand Delta

0

- 60

%

SHED_DEL

0

49

SH.TM

Maximum Loadshed Time

0

- 120

min

SHED_TIM

60

49

D.L.S1

Demand Limit Sw.1 Setpt.

0

- 100

%

DLSWSP1

80

31,49

D.L.S2

Demand Limit Sw.2 Setpt.

0

- 100

%

DLSWSP2

50

31,49

IAQ

INDOOR AIR QUALITY CFG.

 

 

 

 

 

 

DCV.C

DCV ECONOMIZER SETPOINTS

 

 

 

 

 

 

DCV.CEC.MN

Economizer Min.Position

0

- 100

%

ECONOMIN

5

29,31,32,67-70

DCV.CIAQ.M

IAQ Demand Vent Min.Pos.

0

- 100

%

IAQMINP

0

29,31,67-70

AQ.CF

AIR QUALITY CONFIGS

 

 

 

 

 

 

AQ.CFIQ.A.C

IAQ Analog Sensor Config

0

- 4 (multi-text strings)

 

IAQANCFG

0

32,67,69,70

AQ.CFIQ.A.F

IAQ 4-20 ma Fan Config

0

- 2 (multi-text strings)

 

IAQANFAN

0

32,68-70

AQ.CFIQ.I.C

IAQ Discrete Input Config

0

- 2 (multi-text strings)

 

IAQINCFG

0

31,35,67-70

AQ.CFIQ.I.F

IAQ Disc.In. Fan Config

0

- 2 (multi-text strings)

 

IAQINFAN

0

32,68-70

AQ.CFOQ.A.C

OAQ 4-20ma Sensor Config

0

- 2 (multi-text strings)

 

OAQANCFG

0

35,68-70

AQ.SP

AIR QUALITY SETPOINTS

 

 

 

 

 

 

AQ.SPIQ.O.P

IAQ Econ Override Pos.

0

- 100

%

IAQOVPOS

100

32,67,69,70,98

AQ.SPDAQ.L

Diff.Air Quality LoLimit

0

- 1000

 

DAQ_LOW

100

68-70

AQ.SPDAQ.H

Diff.Air Quality HiLimit

100 - 2000

 

DAQ_HIGH

700

32,68-70

AQ.SPD.F.OF

DAQ PPM Fan Off Setpoint

0

- 2000

 

DAQFNOFF

200

32,68-70

AQ.SPD.F.ON

DAQ PPM Fan On Setpoint

0

- 2000

 

DAQFNON

400

32,68-70

AQ.SPIAQ.R

Diff. AQ Responsiveness

–5 - 5

 

IAQREACT

0

69,70

AQ.SPOAQ.L

OAQ Lockout Value

0

- 2000

 

OAQLOCK

0

69,70

AQ.SPOAQ.U

User Determined OAQ

0

- 5000

 

OAQ_USER

400

32,69,70

AQ.S.R

AIR QUALITY SENSOR RANGE

 

 

 

 

 

 

AQ.S.RIQ.R.L

IAQ Low Reference

0

- 5000

 

IAQREFL

0

32,69,70

AQ.S.RIQ.R.H

IAQ High Reference

0

- 5000

 

IAQREFH

2000

32,69,70

AQ.S.ROQ.R.L

OAQ Low Reference

0

- 5000

 

OAQREFL

0

69,70

AQ.S.ROQ.R.H

OAQ High Reference

0

- 5000

 

OAQREFH

2000

69,70

IAQ.P

IAQ PRE-OCCUPIED PURGE

 

 

 

 

 

 

IAQ.PIQ.PG

IAQ Purge

 

Yes/No

 

IAQPURGE

No

69,70

IAQ.PIQ.P.T

IAQ Purge Duration

5-60

min

IAQPTIME

15

69,70

IAQ.PIQ.P.L

IAQ Purge LoTemp Min Pos

0-100

%

IAQPLTMP

10

69,70

IAQ.PIQ.P.H

IAQ Purge HiTemp Min Pos

0-100

%

IAQPHTMP

35

69,70

IAQ.PIQ.L.O

IAQ Purge OAT Lockout

35-70

dF

IAQPNTLO

50

69,70

DEHU

DEHUMIDIFICATION CONFIG.

 

 

 

 

 

 

D.SEL

Dehumidification Config

0-2 (multi-text strings)

 

DHSELECT

0

69-71

D.SEN

Dehumidification Sensor

1-2 (multi-text strings)

 

DHSENSOR

1

69,70

D.EC.D

Econ disable in DH mode?

Yes/No

 

DHECDISA

Yes

69,70

D.V.CF

Vent Reheat Setpt Select

0-1 (multi-text strings)

 

DHVHTCFG

0

70,71

D.V.RA

Vent Reheat RAT offset

0-8

^F

DHVRAOFF

0

70,71

D.V.HT

Vent Reheat Setpoint

55-95

dF

DHVHT_SP

70

70,71

D.C.SP

Dehumidify Cool Setpoint

40-55

dF

DHCOOLSP

45

70,71

D.RH.S

Dehumidify RH Setpoint

10-90

%

DHRELHSP

55

70,71