Table 52 — Staging Sequence with Hot Gas Bypass — 48/50AK,AY020-027 and Multi-Stage 48/50AJ,AW020-027

STAGE

 

 

SEQUENCE 1

 

 

 

 

SEQUENCE 2

 

 

0

1

2

3

 

4

5

0

1

2

3

 

4

5

 

 

 

COMP

 

 

Compressor Status

 

 

 

 

Compressor Status

 

 

A1

OFF

ON*

ON

ON

 

OFF

ON

OFF

OFF

OFF

ON

 

ON

ON

A2

OFF

OFF

OFF

ON

 

ON

ON

OFF

ON*

ON

ON

 

OFF

ON

B1

OFF

OFF

OFF

OFF

 

ON

ON

OFF

OFF

OFF

OFF

 

ON

ON

UNIT

 

 

Unit Capacity 48/50A

 

 

 

 

Unit Capacity 48/50A

 

 

020

0%

18%

33%

67%

 

67%

100%

0%

18%

33%

67%

 

67%

100%

025

0%

17%

30%

65%

 

70%

100%

0%

22%

35%

65%

 

65%

100%

027

0%

21%

33%

67%

 

67%

100%

0%

21%

33%

67%

 

67%

100%

*With Minimum Load Valve ON.

Table 53 — Staging Sequence without Hot Gas Bypass — 48/50AK,AY030-060 and Multi-Stage 48/50AJ,AW030-060

STAGE

 

 

SEQUENCE 1

 

 

 

 

SEQUENCE 2

 

 

0

1

2

3

 

4

5

0

1

2

3

 

4

5

 

 

 

COMP

 

 

Compressor Status

 

 

 

 

Compressor Status

 

 

A1

OFF

ON

ON

OFF

 

ON

ON

OFF

OFF

ON

ON

 

ON

ON

A2

OFF

OFF

ON

ON

 

ON

ON

OFF

ON

ON

OFF

 

ON

ON

B1

OFF

OFF

OFF

ON

 

ON

ON

OFF

OFF

OFF

OFF

 

OFF

ON

B2

OFF

OFF

OFF

OFF

 

OFF

ON

OFF

OFF

OFF

ON

 

ON

ON

UNIT

 

 

Unit Capacity 48/50A

 

 

 

 

Unit Capacity 48/50A

 

 

030

0%

23%

45%

50%

 

73%

100%

0%

23%

45%

50%

 

73%

100%

035,036

0%

22%

48%

52%

 

74%

100%

0%

26%

48%

48%

 

74%

100%

040,041

0%

21%

43%

50%

 

71%

100%

0%

21%

43%

50%

 

72%

100%

050

0%

23%

46%

46%

 

68%

100%

0%

23%

46%

54%

 

77%

100%

051

0%

25%

50%

50%

 

75%

100%

0%

25%

50%

50%

 

75%

100%

060

0%

24%

50%

50%

 

74%

100%

0%

26%

50%

50%

 

76%

100%

Table 54 — Staging Sequence with Hot Gas Bypass — 48/50AK,AY030-060

STAGE

 

 

 

SEQUENCE 1

 

 

 

 

 

SEQUENCE 2

 

 

0

1

2

 

3

4

5

6

0

1

2

 

3

4

5

6

 

 

 

COMP

 

 

Compressor Status

 

 

 

 

Compressor Status

 

 

A1

OFF

ON*

ON

 

ON

OFF

ON

ON

OFF

OFF

OFF

 

ON

ON

ON

ON

A2

OFF

OFF

OFF

 

ON

ON

ON

ON

OFF

ON*

ON

 

ON

OFF

ON

ON

B1

OFF

OFF

OFF

 

OFF

ON

ON

ON

OFF

OFF

OFF

 

OFF

OFF

OFF

ON

B2

OFF

OFF

OFF

 

OFF

OFF

OFF

ON

OFF

OFF

ON

 

OFF

ON

ON

ON

UNIT

 

 

Unit Capacity 48/50A

 

 

 

 

Unit Capacity 48/50A

 

 

030

0%

12%

23%

 

45%

50%

73%

100%

0%

12%

23%

 

45%

50%

73%

100%

035,036

0%

12%

22%

 

48%

52%

74%

100%

0%

16%

26%

 

48%

48%

74%

100%

040,041

0%

13%

21%

 

43%

50%

71%

100%

0%

13%

21%

 

43%

50%

72%

100%

050

0%

16%

23%

 

46%

46%

68%

100%

0%

16%

23%

 

46%

54%

77%

100%

051

0%

19%

25%

 

50%

50%

75%

100%

0%

19%

25%

 

50%

50%

75%

100%

060

0%

19%

24%

 

50%

50%

74%

100%

0%

21%

26%

 

50%

50%

76%

100%

*With minimum load valve ON.

Table 55 — 2-Stage Sequence —

48/50A2,A4020-027

STAGE

 

SEQUENCE 1

 

SEQUENCE 2

0

 

1

2

0

 

1

2

 

 

 

 

Thermostat Inputs

Thermostat Inputs

Y1

OPEN

CLOSED

CLOSED

OPEN

CLOSED

CLOSED

Y2

OPEN

 

OPEN

CLOSED

OPEN

 

OPEN

CLOSED

COMP

Compressor Status

Compressor Status

A1

OFF

 

ON

ON

OFF

 

OFF

ON

A2

OFF

 

OFF

ON

OFF

 

ON

ON

B1

OFF

 

OFF

ON

OFF

 

OFF

ON

UNIT

 

 

Unit Capacity

 

Unit Capacity

020

0%

 

30%

100%

0%

 

30%

100%

025

0%

 

33%

100%

0%

 

33%

100%

027

0%

 

33%

100%

0%

 

33%

100%

Table 56 — 2-Stage Sequence —

48/50A2,A4030-060

STAGE

 

SEQUENCE 1

 

SEQUENCE 2

0

 

1

2

0

 

1

2

 

 

 

 

Thermostat Inputs

Thermostat Inputs

Y1

OPEN

CLOSED

CLOSED

OPEN

CLOSED

CLOSED

Y2

OPEN

 

OPEN

CLOSED

OPEN

 

OPEN

CLOSED

COMP

Compressor Status

Compressor Status

A1

OFF

 

ON

ON

OFF

 

OFF

ON

A2

OFF

 

OFF

ON

OFF

 

ON

ON

B1

OFF

 

ON

ON

OFF

 

OFF

ON

B2

OFF

 

OFF

ON

OFF

 

ON

ON

UNIT

 

Unit Capacity

 

Unit Capacity

030

0%

 

50%

100%

0%

 

50%

100%

035

0%

 

50%

100%

0%

 

50%

100%

040

0%

 

50%

100%

0%

 

50%

100%

050

0%

 

50%

100%

0%

 

50%

100%

060

0%

 

50%

100%

0%

 

50%

100%

44

Page 44
Image 44
Carrier 48/50AJ specifications Staging Sequence with Hot Gas Bypass 48/50AK,AY030-060, Stage Sequence 48/50A2,A4020-027