Table 84 — Indoor Air Quality Configuration

ITEM

EXPANSION

 

 

RANGE

 

UNITS

 

CCN POINT

 

DEFAULT

DCV.C

DCV ECONOMIZER SETPOINTS

 

 

 

 

 

 

 

 

 

EC.MN

Economizer Min.Position

 

0

- 100

 

%

 

ECONOMIN

 

5

 

 

 

 

IAQ.M

IAQ Demand Vent Min.Pos.

 

0

- 100

 

%

 

IAQMINP

 

0

AQ.CF

AIR QUALITY CONFIGS

 

 

 

 

 

 

 

 

 

IQ.A.C

IAQ Analog Sensor Config

 

0

- 4

 

 

 

IAQANCFG

 

0

 

 

 

 

 

IQ.A.F

IAQ 4-20 ma Fan Config

 

0

- 2

 

 

 

IAQANFAN

 

0

IQ.I.C

IAQ Discrete Input Config

 

0

- 2

 

 

 

IAQINCFG

 

0

IQ.I.F

IAQ Disc.In. Fan Config

 

0

- 2

 

 

 

IAQINFAN

 

0

OQ.A.C

OAQ 4-20ma Sensor Config

 

0

- 2

 

 

 

OAQANCFG

 

0

AQ.SP

AIR QUALITY SETPOINTS

 

 

 

 

 

 

 

 

 

IQ.O.P

IAQ Econo Override Pos.

 

0

- 100

 

%

 

IAQOVPOS

 

100

 

 

 

 

DAQ.L

Diff.Air Quality LoLimit

 

0

- 1000

 

 

 

DAQ_LOW

 

100

DAQ.H

Diff. Air Quality HiLimit

 

100 - 2000

 

 

 

DAQ_HIGH

 

700

D.F.OF

DAQ PPM Fan Off Setpoint

 

0

- 2000

 

 

 

DAQFNOFF

 

200

D.F.ON

DAQ PPM Fan On Setpoint

 

0

- 2000

 

 

 

DAQFNON

 

400

IAQ.R

Diff. AQ Responsiveness

 

-5 - 5

 

 

 

IAQREACT

 

0

OAQ.L

OAQ Lockout Value

 

0

- 2000

 

 

 

OAQLOCK

 

0

OAQ.U

User Determined OAQ

 

0

- 5000

 

 

 

OAQ_USER

 

400

AQ.S.R

AIR QUALITY SENSOR RANGE

 

 

 

 

 

 

 

 

 

IQ.R.L

IAQ Low Reference

 

0

- 5000

 

 

 

IAQREFL

 

0

 

 

 

 

 

IQ.R.H

IAQ High Reference

 

0

- 5000

 

 

 

IAQREFH

 

2000

OQ.R.L

OAQ Low Reference

 

0

- 5000

 

 

 

OAQREFL

 

0

OQ.R.H

OAQ High Reference

 

0

- 5000

 

 

 

OAQREFH

 

2000

IAQ.P

IAQ PRE-OCCUPIED PURGE

 

 

 

 

 

 

 

 

 

IQ.PG

IAQ Purge

 

Yes/No

 

 

 

IAQPURGE

 

No

 

 

 

 

 

IQ.P.T

IAQ Purge Duration

 

5

- 60

 

min

 

IAQPTIME

 

15

IQ.P.L

IAQ Purge LoTemp Min Pos

 

0

- 100

 

%

 

IAQPLTMP

 

10

IQ.P.H

IAQ Purge HiTemp Min Pos

 

0

- 100

 

%

 

IAQPHTMP

 

35

IQ.L.O

IAQ Purge OAT Lockout

 

35 - 70

 

dF

 

IAQPNTLO

 

50

Table 85 — Dehumidification Configuration

ITEM

EXPANSION

 

RANGE

UNITS

CCN POINT

 

DEFAULT

DEHU

DEHUMIDIFICATION CONFIG.

 

 

 

 

 

 

D.SEL

Dehumidification Config

 

0-2

 

DHSELECT

 

0

 

 

 

D.SEN

Dehumidification Sensor

 

1-2

 

DHSENSOR

 

1

D.EC.D

Econ disable in DH mode?

 

Yes/No

 

DHECDISA

 

Yes

D.V.CF

Vent Reheat Setpt Select

 

0-1

 

DHVHTCFG

 

0

D.V.RA

Vent Reheat RAT offset

 

0-8

^F

DHVRAOFF

 

0

D.V.HT

Vent Reheat Setpoint

 

55-95

dF

DHVHT_SP

 

70

D.C.SP

Dehumidify Cool Setpoint

 

40-55

dF

DHCOOLSP

 

45

D.RH.S

Dehumidify RH Setpoint

 

10-90

%

DHRELHSP

 

55

Vent Reheat Set Point Select (D.V.CF) — This configuration determines how the vent reheat set point is selected.

D.V.CF = 0 — Reheat follows an offset subtracted from return air temperature (D.V.RA).

D.V.CF = 1 — Reheat follows a dehumidification heat set point (D.V.HT).

Vent Reheat RAT Offset (D.V.RA) — Set point offset used only during the vent mode. The air will be reheated to return- air temperature less this offset.

Vent Reheat Set Point (D.V.HT) — Set point used only dur- ing the vent mode. The air will be reheated to this set point. Dehumidify Cool Set Point (D.C.SP) — This is the dehu- midification cooling set point.

Dehumidity RH Set Point (D.RH.S) — This is the dehumidi- fication relative humidity trip point.

OPERATION — Dehumidification and reheat can only occur if the unit is equipped with either staged gas or hydronic heat. Dehumidification without reheat can be done on any unit but ConfigurationDEHUD.SEL must be set to 2.

If the machine’s control type is a TSTAT type (Configura- tionUNITC.TYP=3 or 4) and the discrete input selection for the sensor is not configured (D.SEN not equal to 2), dehumidification will be disabled.

If the machine’s control type is a TSTAT type (Configura- tionUNITC.TYP=3 or 4) and the economizer is able to provide cooling, a dehumidification mode may be called out, but the control will not request mechanical cooling.

If a 2-stage control type is selected (ConfigurationUNIT C.TYP = 4 or 6), then the economizer, if active, locks out mechanical cooling during the Dehumidification mode.

NOTE: Configuring ConfigurationDEHUD.SEN to 2 will enable the CEM board along with the sensor selected for control.

NOTE: If ConfigurationDEHUD.SEL = 1 or 2, then staged gas control will be automatically enabled (Configura- tionHEATHT.CF will be set to 3).

If a tempering, unoccupied or “mechanical cooling locked out” HVAC mode is present, dehumidification will be disabled. An HVAC Off, Vent or Cool mode must be in effect to launch either a Reheat or Dehumidification mode.

If an associated sensor responsible for dehumidification fails, dehumidification will not be attempted (SPRH, RARH).

Initiating a Reheat or Dehumidification Mode — To call out a Reheat mode in the Vent or the Off HVAC mode, or to call out a Dehumidification mode in a Cool HVAC mode, one of the following conditions must be true:

The space is occupied and the humidity is greater than the relative humidity trip point (D.RH.S).

The space is occupied and the discrete humidity input is closed.

Dehumidification and Reheat Control — If a dehumidifica- tion mode is initiated, the rooftop will attempt to lower humidity as follows:

Economizer Cooling — The economizer, if allowed to perform free cooling, will have its control point (Run StatusVIEWEC.C.P) set to ConfigurationDEHU D.C.SP. If ConfigurationDEHUD.EC.D is dis- abled, the economizer will always be disabled during dehumidification.

Cooling — For all cooling control types: A High Cool HVAC mode will be requested internally to the control to

70

Page 70
Image 70
Carrier 48/50AJ specifications Indoor Air Quality Configuration, Dehumidification Configuration