APPENDIX A — LOCAL DISPLAY TABLES (cont)

MODE — PRESSURES

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

WRITE STATUS

AIR.P

AIR PRESSURES

 

 

 

 

SP

Static Pressure

 

"H2O

SP

 

BP

Building Pressure

 

"H2O

BP

 

REF.P

REFRIGERANT PRESSURES

 

 

 

 

DP.A

Cir A Discharge Pressure

 

PSIG

DP_A

 

SP.A

Cir A Suction Pressure

 

PSIG

SP_A

 

DP.B

Cir B Discharge Pressure

 

PSIG

DP_B

 

SP.B

Cir B Suction Pressure

 

PSIG

SP_B

 

MODE — SET POINTS

ITEM

DESCRIPTION

RANGE

UNITS

CCN POINT

DEFAULT

OHSP

Occupied Heat Setpoint

40-99

dF

OHSP

68

OCSP

Occupied Cool Setpoint

40-99

dF

OCSP

75

UHSP

Unoccupied Heat Setpoint

40-99

dF

UHSP

55

UCSP

Unoccupied Cool Setpoint

40-99

dF

UCSP

90

GAP

Heat-Cool Setpoint Gap

2-10

^F

HCSP_GAP

5

V.C.ON

VAV Occ. Cool On Delta

0-25

^F

VAVOCON

3.5

V.C.OF

VAV Occ. Cool Off Delta

1-25

^F

VAVOCOFF

2

SASP

Supply Air Setpoint

45-75

dF

SASP

55

SA.HI

Supply Air Setpoint Hi

45-75

dF

SASP_HI

55

SA.LO

Supply Air Setpoint Lo

45-75

dF

SASP_LO

60

SA.HT

Heating Supply Air Setpt

80-120

dF

SASPHEAT

85

T.PRG

Tempering Purge SASP

–20-80

dF

TEMPPURG

50

T.CL

Tempering in Cool SASP

5-75

dF

TEMPCOOL

5

T.V.OC

Tempering Vent Occ SASP

–20-80

dF

TEMPVOCC

65

T.V.UN

Tempering Vent Unocc. SASP

–20-80

dF

TEMPVUNC

50

MODE — INPUTS

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

WRITE STATUS

GEN.I

GENERAL INPUTS

 

 

 

 

FLT.S

Filter Status Input

DRTY/CLN

 

FLTS

forcible

G.FAN

Fan Request From IGC

ON/OFF

 

IGCFAN

 

REMT

Remote Input State

*

 

RMTIN

forcible

E.SW

Economizer Control Input

YES/NO

 

ECOSW

forcible

E.ENA

Remote Economizer Enable

YES/NO

 

ECONENBL

forcible

E.OVR

Econo Position Override

YES/NO

 

ECOORIDE

forcible

S.FN.S

Supply Fan Status Switch

ON/OFF

 

SFS

forcible

DL.S1

Demand Limit Switch 1

ON/OFF

 

DMD_SW1

forcible

DL.S2

Demand Limit Switch 2

ON/OFF

 

DMD_SW2

forcible

DH.IN

Dehumidify Switch Input

ON/OFF

 

DHDISCIN

forcible

FD.BK

COMPRESSOR FEEDBACK

 

 

 

 

CS.A1

Compressor A1 Feedback

ON/OFF

 

CSB_A1

 

CS.A2

Compressor A2 Feedback

ON/OFF

 

CSB_A2

 

CS.B1

Compressor B1 Feedback

ON/OFF

 

CSB_B1

 

CS.B2

Compressor B2 Feedback

ON/OFF

 

CSB_B2

 

STAT

THERMOSTAT INPUTS

 

 

 

 

G

Thermostat G Input

ON/OFF

 

G

forcible

W1

Thermostat W1 Input

ON/OFF

 

W1

forcible

W2

Thermostat W2 Input

ON/OFF

 

W2

forcible

Y1

Thermostat Y1 Input

ON/OFF

 

Y1

forcible

Y2

Thermostat Y2 Input

ON/OFF

 

Y2

forcible

FIRE

FIRE-SMOKE INPUTS

 

 

 

 

FSD

Fire Shutdown Input

ALARM/NORMAL

 

FSD

forcible

PRES

Pressurization Input

ALARM/NORMAL

 

PRES

forcible

EVAC

Evacuation Input

ALARM/NORMAL

 

EVAC

forcible

PURG

Smoke Purge Input

ALARM/NORMAL

 

PURG

forcible

REL.H

RELATIVE HUMIDITY

 

 

 

 

OA.RH

Outside Air Rel. Humidity

 

%

OARH

forcible

OA.EN

Outdoor Air Enthalpy

 

 

OAE

 

OA.DP

OutsideAir Dewpoint Temp

 

dF

OADEWTMP

 

RA.RH

Return Air Rel. Humidity

 

%

RARH

forcible

RA.EN

Return Air Enthalpy

 

 

RAE

 

AIR.Q

AIR QUALITY SENSORS

 

 

 

 

IAQ.I

IAQ - Discrete Input

HIGH/LOW

 

IAQIN

forcible

IAQ

IAQ - PPM Return CO2

 

 

IAQ

forcible

OAQ

OAQ - PPM Return CO2

 

 

OAQ

forcible

DAQ

Diff.Air Quality in PPM

 

 

DAQ

 

IQ.P.O

IAQ Min.Pos. Override

 

%

IAQMINOV

forcible

RSET

RESET INPUTS

 

 

 

 

SA.S.R

Supply Air Setpnt. Reset

 

^F

SASPRSET

forcible

SP.RS

Static Pressure Reset

 

 

SPRESET

forcible

*The display text changes depending on the remote switch configuration (ConfigurationUNITRM.CF). If RM.CF is set to 0 (No Remote Switch), then the display text will be “On” or “Off.” If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or “Unoccupied.” If RM.CF is set to 2 (Start/Stop), then the display text will be “Stop” or “Start.” If RM.CF is set to 3 (Override Switch), then the display text will be “No Override” or “Override.”

142

Page 142
Image 142