APPENDIX B — CCN TABLES (cont)

MAINTENANCE DISPLAY TABLES (cont)

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

PRESBLDG

Building Pressure

 

"H2O

BP

 

 

 

 

 

Econo Damper Current Pos

 

%

ECONOPOS

 

 

Power Exhaust Stage A

 

 

PE_A

 

 

Power Exhaust Stage B

 

 

PE_B

 

 

Power Exhaust Stage C

 

 

PE_C

 

 

BP Load Factor

 

 

BPSMZ

 

 

BP Rise Per Stage

 

 

BPRISE

 

 

BP PID/Integral Term

 

 

BPINT

config

 

BP PID Threshold

 

 

BPZ

config

 

BP Deadband

 

 

BPY

config

 

Building Pressure Error

 

 

BPERROR

config

 

Rate of Chng of BPERROR

 

 

BPRATE

config

 

High BP Override

 

 

BPHPOVRD

config

 

Low BP Override

 

 

BPLPOVRD

config

PRESDUCT

Static Pressure

 

"H2O

SP

 

 

 

 

 

Supply Fan VFD Speed

 

%

SFAN_VFD

 

 

Static Pressure Setpoint

 

"H2O

SPSP

config

 

Static Pressure Reset

 

 

SPRESET

forcible

STAGEGAS

Heating Mode………..:

 

 

 

 

 

 

 

 

 

 

Requested Heat Stage

 

 

HT_STAGE

 

 

Heating Control Point

 

 

HEATCPNT

 

 

Staged Gas LAT Sum

 

dF

LAT_SGAS

 

 

Staged Gas LAT 1

 

dF

LAT1SGAS

 

 

Staged Gas LAT 2

 

dF

LAT2SGAS

 

 

Staged Gas LAT 3

 

dF

LAT3SGAS

 

 

Staged Gas Limit Sw.Temp

 

dF

LIMSWTMP

 

 

Heat PID Timer

 

sec

HTSGTIMR

 

 

Staged Gas Capacity Calc

 

%

HTSGCALC

 

 

Current Running Capacity

 

%

HTSG_CAP

 

 

Proportional Cap. Change

 

 

HTSG_P

 

 

Derivative Cap. Change

 

 

HTSG_D

 

 

Maximum Heat Stages

 

 

HTMAXSTG

 

 

Hi Limit Switch Tmp Mode

 

 

LIMTMODE

 

 

LAT Cutoff Mode

 

 

LATCMODE

 

 

Capacity Clamp Mode

 

 

CAPMODE

 

STRTHOUR

Compressor A1 Run Hours

 

hours

HR_A1

config

 

 

 

Compressor A2 Run Hours

 

hours

HR_A2

config

 

Compressor B1 Run Hours

 

hours

HR_B1

config

 

Compressor B2 Run Hours

 

hours

HR_B2

config

 

Compressor A1 Starts

 

 

CY_A1

config

 

Compressor A2 Starts

 

 

CY_A2

config

 

Compressor B1 Starts

 

 

CY_B1

config

 

Compressor B2 Starts

 

 

CY_B2

config

SUMZ

Cooling Control Point

 

dF

COOLCPNT

 

 

 

 

 

Mixed Air Temperature

 

dF

MAT

 

 

Evaporator Discharge Tmp

 

dF

EDT

 

 

Return Air Temperature

 

dF

RAT

 

 

Outside Air Temperature

 

dF

OAT

 

 

Econo Damper Current Pos

 

%

ECONOPOS

 

 

Capacity Threshold Adjst

 

 

Z_GAIN

 

 

Capacity Load Factor

 

 

SMZ

 

 

Next Stage EDT Decrease

 

 

ADDRISE

 

 

Next Stage EDT Increase

 

 

SUBRISE

 

 

Rise Per Percent Capacity

 

 

RISE_PCT

 

 

Cap Deadband Subtracting

 

 

Y_MINUS

 

 

Cap Deadband Adding

 

 

Y_PLUS

 

 

Cap Threshold Subtracting

 

 

Z_MINUS

 

 

Cap Threshold Adding

 

 

Z_PLUS

 

 

High Temp Cap Override

On/Off

 

HI_TEMP

 

 

Low Temp Cap Override

On/Off

 

LOW_TEMP

 

 

Pull Down Cap Override

On/Off

 

PULLDOWN

 

 

Slow Change Cap Override

On/Off

 

SLO_CHNG

 

SYSTEM

Reset All Current Alarms

Yes/No

 

ALRESET

config

 

 

 

Reset the Device

Yes/No

 

RESETDEV

config

 

Local Machine Disable

Yes/No

 

UNITSTOP

config

 

Soft Stop Request

Yes/No

 

SOFTSTOP

forcible

 

Emergency Stop

Enable/Disable

 

EMSTOP

forcible

 

CEM AN1 10K temp J5,1-2

-40 - 240

dF

CEM10K1

forcible

 

CEM AN2 10K temp J5,3-4

-40 - 240

dF

CEM10K2

forcible

 

CEM AN3 10K temp J5,5-6

-40 - 240

dF

CEM10K3

forcible

 

CEM AN4 10K temp J5,7-8

-40 - 240

dF

CEM10K4

forcible

 

CEM AN1 4-20 ma J5,1-2

0-20

ma

CEM4201

forcible

 

CEM AN2 4-20 ma J5,3-4

0-20

ma

CEM4202

forcible

 

CEM AN3 4-20 ma J5,5-6

0-20

ma

CEM4203

forcible

 

CEM AN4 4-20 ma J5,7-8

0-20

ma

CEM4204

forcible

159

Page 159
Image 159