Carrier 48/50AJ APPENDIX A — LOCAL DISPLAY TABLES cont, MODE - INPUTS cont, Mode — Outputs

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 143
Image 143
MODE — INPUTS (cont)

APPENDIX A — LOCAL DISPLAY TABLES (cont)

MODE — INPUTS (cont)

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

WRITE STATUS

4-20

4-20 MILLIAMP INPUTS

 

 

 

 

IAQ.M

IAQ Milliamps

 

ma

IAQ_MA

 

OAQ.M

OAQ Milliamps

 

ma

OAQ_MA

 

SP.R.M

SP Reset milliamps

 

ma

SPRST_MA

 

DML.M

4-20 ma Demand Signal

 

ma

DMDLMTMA

forcible

EDR.M

EDT Reset Milliamps

 

ma

EDTRESMA

 

ORH.M

OARH Milliamps

 

ma

OARH_MA

 

RRH.M

RARH Milliamps

 

ma

RARH_MA

 

BP.M

BP Milliamps

 

ma

BP_MA

 

BP.M.T

Bldg. Pressure Trim (ma)

–2.0 - 2.0

 

BPMATRIM

config

SP.M

SP Milliamps

 

ma

SP_MA

 

SP.M.T

Static Press. Trim (ma)

–2.0 - 2.0

 

SPMATRIM

config

*The display text changes depending on the remote switch configuration (ConfigurationUNITRM.CF). If RM.CF is set to 0 (No Remote Switch), then the display text will be “On” or “Off.” If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or “Unoccupied.” If RM.CF is set to 2 (Start/Stop), then the display text will be “Stop” or “Start.” If RM.CF is set to 3 (Override Switch), then the display text will be “No Override” or “Override.”

MODE — OUTPUTS

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

WRITE STATUS

FANS

FANS

 

 

 

 

S.FAN

Supply Fan Relay

ON/OFF

 

SFAN_RLY

 

S.VFD

Supply Fan VFD Speed

0-100

%

SFAN_VFD

 

P.E.A

Power Exhaust Relay A

ON/OFF

 

PE_A

 

P.E.B

Power Exhaust Relay B

ON/OFF

 

PE_B

 

P.E.C

Power Exhaust Relay C

ON/OFF

 

PE_C

 

CD.F.A

Condenser Fan Circuit A

ON/OFF

 

CONDFANA

 

CD.F.B

Condenser Fan Circuit B

ON/OFF

 

CONDFANB

 

COOL

COOLING

 

 

 

 

A1

Compressor A1 Relay

ON/OFF

 

CMPA1

 

A2

Compressor A2 Relay

ON/OFF

 

CMPA2

 

MLV

Min. Load Valve (HGBP)

ON/OFF

 

MLV

 

B1

Compressor B1 Relay

ON/OFF

 

CMPB1

 

B2

Compressor B2 Relay

ON/OFF

 

CMPB2

 

HEAT

HEATING

 

 

 

 

HT.1

Heat Relay 1

ON/OFF

 

HS1

 

HT.2

Heat Relay 2

ON/OFF

 

HS2

 

HT.3

Relay 3 W1 Gas Valve 2

ON/OFF

 

HS3

 

HT.4

Relay 4 W2 Gas Valve 2

ON/OFF

 

HS4

 

HT.5

Relay 5 W1 Gas Valve 3

ON/OFF

 

HS5

 

HT.6

Relay 6 W2 Gas Valve 3

ON/OFF

 

HS6

 

H.I.R

Heat Interlock Relay

ON/OFF

 

HIR

forcible

ECON

ECONOMIZER

 

 

 

 

ECN.P

Economizer Act.Curr.Pos.

0-100

%

ECONOPOS

 

ECN.C

Economizer Act.Cmd.Pos.

0-100

%

ECONOCMD

forcible

E.PWR

Economizer Power Relay

ON/OFF

 

ECON_PWR

forcible

GEN.O

GENERAL OUTPUTS

 

 

 

 

ALRM

Remote Alarm/Aux Relay

ON/OFF

 

ALRM

forcible

MODE — CONFIGURATION

ITEM

EXPANSION

 

RANGE

UNITS

CCN POINT

DEFAULT

PAGE NO.

UNIT

UNIT CONFIGURATION

 

 

 

 

 

 

C.TYP

Machine Control Type

1

- 6 (multi-text strings)

 

CTRLTYPE

4

27,28,32,35-37,

 

 

 

 

 

 

63,75,96

CV.FN

 

 

 

 

 

 

Fan Mode (0=Auto, 1=Cont)

0

- 1 (multi-text strings)

 

FAN_MODE

1

27,28,35,36

RM.CF

Remote Switch Config

0

- 3 (multi-text strings)

 

RMTINCFG

0

31,35,36,74

CEM

CEM Module Installed

Yes/No

 

CEM_BRD

No

35,36

TCS.C

Temp.Cmp.Strt.Cool Factr

0

- 60

min

TCSTCOOL

0

35,36

TCS.H

Temp.Cmp.Strt.Heat Factr

0

- 60

min

TCSTHEAT

0

36

SFS.S

Fan Fail Shuts Down Unit

Yes/No

 

SFS_SHUT

No

36,60,100

SFS.M

Fan Stat Monitoring Type

0

- 2 (multi-text strings)

 

SFS_MON

0

35,36,60,100

VAV.S

VAV Unocc.Fan Retry Time

0

- 720

min

SAMPMINS

50

36

SIZE

Unit Size (20-60)

20 - 60

 

UNITSIZE

20

36,38,42,49

DP.XR

Disch.Press. Transducers

Yes/No

 

DP_TRANS

No

36,97

SP.XR

Suct. Pres. Trans. Type

0

- 1 (multi-text strings)

 

SPXRTYPE

0

36

RFG.T

Refrig: 0=R22 1=R410A

0

- 1 (multi-text strings)

 

REFRIG_T

1

36,38,49

CND.T

Cnd HX Typ:0=RTPF 1=MCHX

0

- 1 (multi-text strings)

 

COILTYPE

0

36,38,49

MAT.S

MAT Calc Config

0

- 2 (multi-text strings)

 

MAT_SEL

1

36,47,48

MAT.R

Reset MAT Table Entries?

Yes/No

 

MATRESET

No

36,47,48

MAT.D

MAT Outside Air Default

0-100

%

MATOADOS

20

36,37

ALTI

Altitude……..in feet:

0

- 60000

 

ALTITUDE

0

36,37

DLAY

Startup Delay Time

0

- 900

sec

DELAY

0

36,37

STAT

TSTAT-Both Heat and Cool

Yes/No

 

TSTATALL

No

36,37

AUX.R

Auxiliary Relay Config

0

- 3

 

AUXRELAY

0

36,37

SENS

INPUT SENSOR CONFIG

 

 

 

 

 

36

SENSSPT.S

Space Temp Sensor

Enable/Disable

 

SPTSENS

Disable

27,28,36,37

SENSSP.O.S

Space Temp Offset Sensor

Enable/Disable

 

SPTOSENS

Disable

36,37,75

SENSSP.O.R

Space Temp Offset Range

1

- 10

 

SPTO_RNG

5

36,37,75

SENSRRH.S

Return Air RH Sensor

Enable/Disable

 

RARHSENS

Disable

36,37,61,97,99

SENSFLT.S

Filter Stat.Sw.Enabled ?

Enable/Disable

 

FLTS_ENA

Disable

36,37,60,100

143

Page 143
Image 143
Carrier 48/50AJ APPENDIX A — LOCAL DISPLAY TABLES cont, MODE - INPUTS cont, Mode — Outputs, Mode — Configuration