2.2

REFRIGERATION SYSTEM DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of Cylinders

 

 

6

 

 

 

 

 

 

 

 

 

Model

 

 

06DR

 

 

 

 

 

 

 

 

 

CFM

 

 

41

 

 

 

 

 

 

 

Weight (Dry)

118 kg (260 lb) - Single-Speed

 

 

 

 

 

 

i.

Compressor/Motor Assembly

129.39 kg (285.25 lb) - Two-Speed

 

 

 

 

 

 

 

 

Approved Oil

Castrol Icematic -- SW20

 

 

 

 

 

 

 

Oil Charge

3.6 liters (7.6 U.S. pints)

 

 

 

 

 

 

 

 

The oil level range, with the compressor off,

 

 

Oil Sight Glass

should be between the bottom and one-eighth

 

 

 

level of the capacity of the sight glass.

 

 

Verify at --18 _C

 

 

 

 

j.

Expansion Valve Superheat

(0 _F) container box

4.48 to 6.67 _C (8 to 12 _F)

 

 

temperature

 

 

 

 

k. Heater Termination Thermostat

Opens

54 (¦ 3) _C = 130 (¦ 5) _F

Closes

38 (¦ 4) _C = 100 (¦ 7) _F

l.

High Pressure Switch

Cutout

25 (¦ 1.0) kg/cm@ = 350 (¦ 10) psig

 

 

 

 

 

Cut-In

18 (¦ 0.7) kg/cm@ = 250 (¦ 10) psig

 

 

 

 

 

 

 

 

 

Unit Configuration

Charge Requirements -- R-134a

 

 

 

 

 

 

 

 

2* row condenser

 

4* row condenser

 

 

 

 

m. Refrigerant Charge

 

 

 

 

 

Water-Cooled

4.5 kg (9.0 lbs)

 

 

5.22 kg (11.5 lbs)

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

Receiver

3.74 kg (8.25 lbs)

 

4.88 kg (10.75 lbs)

 

 

 

 

 

 

 

 

 

* Refer to Table 1-1.

 

 

 

 

 

 

 

 

 

 

 

 

NOTE

 

 

 

 

 

When replacing the components (n.), (o.) and (p.) in section 2.2, refer to the installation instructions

 

included with the ordered new part for additional information.

 

 

 

 

 

 

 

n. Fusible Plug

Melting point

99 _C = (210 _F)

 

 

 

 

 

Torque

6.2 to 6.9

mkg (45 to 50 ft-lbs)

 

 

 

 

 

 

o. Sight Glass/Moisture Indicator

Torque

8.9 to 9.7

mkg (65 to 70 ft-lbs)

 

 

Bursts at

35 ￿5% kg/cm@ = (500 ￿5% psig)

 

 

 

 

 

 

 

 

 

Torque

1.4 to 2 mkg (10 to 15 ft-lbs)

p. Rupture Disc

(P/N 14-00215-03)

 

 

 

 

 

 

Torque

6.2 to 6.9

mkg (45 to 50 ft-lbs)

 

 

(P/N 14-00215-04)

 

 

 

 

 

 

 

 

 

The condenser fan will start if the condenser

 

 

Condenser Fan Starts

pressure is greater than 14.06 kg/cm@ (200

 

 

psig) OR the condenser fan is OFF for more

 

 

 

q. Condenser Pressure

 

than 60 seconds.

 

Transducer (CPT)

 

The condenser fan will stop if the condenser

 

 

Condenser Fan Stops

pressure is less than 9.14 kg/cm@ (130 psig)

 

 

AND the condenser fan remains ON for at least

 

 

 

 

 

 

30 seconds.

r.

Unit Weight

Refer to unit model number plate, see Figure 2-1 for location of plate.

 

 

 

s. Water Pressure Switch

Cut-In

0.5 ¦ 0.2 kg/cm@ (7 ¦ 3 psig)

 

(Optional)

Cutout

1.6 ¦ 0.4 kg/cm@ (22 ¦ 5 psig)

T-268-07

2-10

Page 29
Image 29