| REMEDY/ | |
CONDITION | POSSIBLE CAUSE | REFERENCE | |
|
| SECTION | |
5.11 THERMOSTATIC EXPANSION VALVE MALFUNCTION |
| ||
|
|
| |
| Low refrigerant charge | 6.4/6.6 | |
| External equalizer line plugged | Open | |
| Wax, oil or dirt plugging valve or orifice Ice formation at | 6.26 | |
Low suction pressure with high | valve seat |
| |
Superheat too high | 6.4/6.6 | ||
superheat | |||
Power assembly failure | 6.26.c | ||
| |||
| Loss of element/bulb charge | 6.26 | |
| Broken capillary | 6.26 | |
| Foreign material in valve | 6.26 | |
High suction pressure with low | Superheat setting too low | 6.26.c | |
External equalizer line plugged Ice holding valve open | Open | ||
superheat | |||
Foreign material in valve | 6.4/6.5 6.26 | ||
| |||
|
|
| |
Liquid slugging in compressor | Pin and seat of expansion valve eroded or held open by | 6.26 | |
foreign material |
| ||
|
| ||
Fluctuating suction pressure | Improper bulb location or installation | 6.26 | |
Low superheat setting | 6.26.c | ||
| |||
5.12 POWER AUTOTRANSFORMER MALFUNCTION |
| ||
|
|
| |
| Circuit breaker | Check | |
Unit will not start | Power transformer defective | 6.22 | |
Power source not turned ON | Check | ||
| |||
| 460 VAC power plug is not inserted into the receptacle | 2.4 | |
|
|
| |
5.13 |
| ||
|
|
| |
High discharge pressure | Dirty coil | 6.28 | |
Noncondensibles |
| ||
|
| ||
Condenser fan starts and stops | Water pressure switch malfunction | Check | |
Water supply interruption |
| ||
|
|
|