4.4.6Defrost
Refer to section 3.1.4 (Code 27) for description of the defrost interval selector and automatic defrost initiation.
The defrost cycle (see Figure
Defrost may take place any time the DTS allows, and no shutdown alarms are active. With these conditions satisfied, defrost is initiated when one of the following conditions becomes true:
a.The manual defrost switch (MDS) is closed by the user. Refer to Figure
b.The defrost interval timer reaches or exceeds the defrost interval selected and set by the user.
c.During
d.When the probe diagnostic logic determines that a probe check is necessary based on the temperature values currently reported by the supply and return probes.
e.When bulb mode is active, and the defrost termination sensor (DTS) is between 0_C and 10_C (32_F and 50_F).
When the defrost mode is initiated, the controller relay contacts (TH) close to supply power to the heat contactor (HR) and in turn, energize the defrost heaters. The defrost light is illuminated.
Relay TC and TD open to
Relay TE and TV open to stop the evaporator fan motors.
The
When the coil tube sheet temperature reaches 25.6_C (78_F), [4_C and 25.6_C (39.2_F and 78_F) if configured for and operating in bulb mode], the defrost termination sensor (DTS) causes the controller to end the defrost cycle and the unit returns to its normal function. Under certain circumstances, defrost may also be forced to terminate through special communication commands.
Upon completion of the
The 54.5_C (130_F) heat termination thermostat (HTT) will open the circuit if the defrost mode does not terminate at 25.6_C (78_F). If termination does not occur within 2.0 hours, the controller will terminate defrost. An alarm will be given of a possible DTS failure.
When the return air falls to 7_C (45_F), the controller checks to ensure the defrost termination sensor (DTS) has dropped to 10_C or below. If it has not, a DTS failure alarm is given and the defrost mode is operated by the return temperature sensor (RTS).
Snap Freeze Option:
NOTE
Controller configuration variable 33 must be set to SnAP to activate this option, refer to Table
If the probe check portion of defrost is required (depending on the configuration of probe check), snap freeze will run after the probe check cycle. Otherwise, snap freeze will run immediately following the
The snap freeze cycle consists of running the compressor without the evaporator fans running for a period of four minutes with both suction solenoid (SSV) and suction modulation (SMV) valves fully open.
If current limiting activates (see section 3.1.4, Cd32) during snap freeze, the state of the SSV and SMV valves may change. When the snap freeze cycle is completed, defrost is formally terminated.
4.4.7Arctic
With arctic mode enabled, if the ambient is colder than
|