Table 4-2. Electrical Control Positions -- ABOVE --10_C (+14_F), or --5_C (+23_F) optionally

CONTROL CIRCUIT

 

COOLING

Holding Zone

* Dehumidification

HEATING

DEFROST

 

 

 

 

 

 

 

Single-Speed Compressor:

 

 

 

 

 

 

 

 

 

 

 

Compressor Contactor

 

Energized

De-energized

**

**

De-energized

(C)

 

1

 

 

 

 

 

Two-Speed Compressor in high speed mode:

Compressor Contactor

Energized

De-energized

**

**

De-energized

(CH)

1

 

 

 

 

 

 

 

 

 

 

Compressor Contactor

Energized

De-energized

**

**

De-energized

(CS)

1

 

 

 

 

Compressor Contactor

De-energized

De-energized

**

**

De-energized

(CL)

1

 

 

 

 

Two-Speed Compressor in low speed mode:

Compressor Contactor

De-energized

De-energized

**

**

De-energized

(CH)

1

 

 

 

 

 

 

 

Compressor Contactor

De-energized

De-energized

**

**

De-energized

(CS)

1

 

 

 

 

 

 

 

Compressor Contactor

Energized

De-energized

**

**

De-energized

(CL)

1

 

 

 

 

 

 

 

Condenser Fan

Energized

De-energized

Energized

De-energized

De-energized

Contactor (CF)

 

 

 

 

 

 

 

High Speed Evaporator

 

 

Refer to section

 

Refer to

De-energized

Energized

Energized

 

section

Contactor (EF)

3.1.7.a.2

 

2

 

 

 

 

3.1.7.a.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Speed Evaporator

 

 

Refer to section

 

Refer to

 

 

De-energized

De-energized

 

section

De-energized

Contactor (ES)

3.1.7.a.2

 

 

 

 

3.1.7.a.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost Relay (TF)

De-energized

De-energized

De-energized

De-energized

Energized

 

 

 

 

 

 

 

 

Heater Relay (HR)

De-energized

De-energized

Energized

 

Energized

Energized

 

 

 

 

 

 

 

 

INDICATING LIGHTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cool

ON

OFF

ON

 

OFF

OFF

 

 

 

 

 

 

 

 

Defrost

OFF

OFF

OFF

 

OFF

ON

 

 

 

 

 

 

 

 

In-Range

On -- If In-Range (Refer to paragraph 3.1.4, Code 30)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat

OFF

OFF

ON

 

ON

ON

POWER CIRCUIT

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

Energized

De-energized

Energized

De-energized

De-energized

 

 

 

 

 

 

Condenser Fan Motor

Energized

De-energized

Energized

De-energized

De-energized

 

 

 

 

 

 

 

Heaters

De-energized

De-energized

Energized

 

Energized

Energized

 

 

 

 

 

 

 

Evaporator Fan Motors

Energized

Energized

Energized

 

Energized

De-energized

 

 

 

 

 

 

 

 

SECTION 4

*Unit with optional Humidity sensor

**Dehumidification and heating modes do not operate at set points below -10_C (14_F), or -5_C (23_F) optionally 1 - May be energized in defrost if snap freeze portion of defrost is run.

2 - May be energized in defrost if probe check portion of defrost is run.

4-15

T-268-07

Page 90
Image 90
Carrier 69NT40-511-199, 69NT40-521 manual Holding Zone