Table 3-7. DataCORDER Alarm Indications

 

 

 

To Access: Press ALT. MODE key

 

 

 

 

CODE #

TITLE

DESCRIPTION

 

 

 

 

 

The recorder supply air temperature is sensed outside of the range of

 

 

--50_C to 70_C (--58_F to +158_F) or if the probe check logic has

 

Recorder Supply

determined there is a fault with this sensor.

AL70

Temperature Out of

NOTE

 

Range

 

The P5 Pre-Trip test must be run to inactivate the alarm (refer to section

 

 

 

 

3.2.1).

 

 

 

 

 

The recorder return air temperature is sensed outside of the range of

 

 

--50_C to 70_C (--58_F to +158_F) or if the probe check logic has

 

Recorder Return

determined there is a fault with this sensor.

AL71

Temperature Out of

NOTE

 

Range

 

The P5 Pre-Trip test must be run to inactivate the alarm (refer to section

 

 

 

 

3.2.1).

 

 

 

AL72-74

USDA Temperatures 1,

The USDA probe temperature reading is sensed outside of range.

2, 3 Out of Range

 

 

AL75

Cargo Probe 4 Out of

The cargo probe temperature reading is sensed outside of range.

Range

 

 

AL76, 77

Future Expansion

These alarms are for future expansion, and are not in use at this time.

 

 

 

AL78-85

Network Sensors 1 -- 8

The network sensor is outside of its specified range. See NOTE below.

Out of Range

 

 

 

 

NOTE

While the DataCORDER is normally setup to record only supply and return recorder sensors, the DataCORDER has the capability to record the data of eight additional sensors. Any sensor installed on the unit may be recorded, and are identifiable as Network Sensors AL 78 to AL85. Which alarm (AL78 to AL 85) is associated with the physical sensor, depends on how the DataCORDER was configured. To identify which sensor is at fault, the unit must be interrogated to locate the sensor being recorded. Generally, the humidity sensor is AL78, as it is the only network sensor recorded.

AL86

RTC Battery Low

The Real Time Clock (RTC) backup battery is too low to adequately

maintain the RTC reading.

 

 

 

 

An invalid date or time has been detected. This situation may be corrected

AL87

RTC Failure

by changing the Real Time Clock (RTC) to a valid value using the

 

 

DataView.

AL88

DataCORDER

A write of critical DataCORDER information to the EEPROM has failed.

EEPROM Failure

 

 

AL89

Flash Memory Error

An error has been detected in the process of writing daily data to the

non-volatile FLASH memory.

 

 

AL90

Future Expansion

This alarm is for future expansion, and is not in use at this time.

 

 

 

AL91

Alarm List Full

The DataCORDER alarm queue is determined to be full (eight alarms).

T-268-07

3-28

Page 66
Image 66
Carrier 69NT40-511-199, 69NT40-521 manual DataCORDER Alarm Indications