CODE | TITLE | DESCRIPTION | |
# | |||
|
| ||
|
| Alarm 53 is caused by the nicad battery pack being too low of a charge for | |
| NiCad Battery Pack | ||
AL53 | NOTE | ||
Failure | |||
|
| Check for recharging or replacing battery pack. | |
|
|
| |
|
| Alarm 54 is activated by an invalid primary supply sensor reading that is sensed | |
|
| outside the range of | |
|
| has determined there is a fault with this sensor. If Alarm 54 is activated and the | |
| Primary Supply Air | primary supply is the control sensor, the secondary supply sensor will be used for | |
| control if the unit is so equipped. If the unit does not have a secondary supply | ||
AL54 | Sensor Failure | ||
probe, and AL54 is activated, the (primary return sensor, minus 2_C) will be used | |||
| (STS) | ||
| for control. | ||
|
| ||
|
| NOTE | |
|
| The P5 | |
|
|
| |
| DataCORDER | This alarm has been activated to indicate the DataCORDER has been disabled | |
AL55 | due to internal failure. To clear this alarm, simply reconfigure the unit to its OEM | ||
| Failure | model number by using the | |
|
| ||
|
|
| |
|
| Alarm 56 is activated by an invalid primary return sensor reading that is outside | |
|
| the range of | |
| Primary Return Air | primary return is the control sensor, the secondary return sensor will be used for | |
| control if the unit is so equipped. If the unit is not equipped with a secondary | ||
AL56 | Sensor Failure | ||
return sensor or it fails, the primary supply sensor will be used for control. | |||
| (RTS) | ||
| NOTE | ||
|
| ||
|
| The P5 | |
|
|
| |
| Ambient | Alarm 57 is triggered by an ambient temperature reading outside the valid range | |
AL57 | Temperature Sensor | ||
| Failure (AMBS) | from | |
|
| ||
|
|
| |
| Compressor High | Alarm 58 is triggered when the compressor high discharge pressure safety switch | |
AL58 | Pressure Safety | (HPS) remains open for at least one minute. This alarm will remain active until the | |
| (HPS) | pressure switch resets, at which time the compressor will restart. | |
|
|
| |
| Heat Termination | Alarm 59 is triggered by the opening of the heat termination thermostat (HTT) and | |
AL59 | Thermostat (HTT) | will result in the disabling of the heater. This alarm will remain active until the | |
| Safety | thermostat resets. | |
|
| Alarm 60 is an indication of a probable failure of the defrost termination sensor | |
|
| (DTS). It is triggered by the opening of the heat termination thermostat (HTT) or | |
| Defrost Termination | the failure of the DTS to go above 25.6_C (78_F) within two hours of defrost | |
| initiation. After | ||
AL60 | Sensor Failure | continuous compressor run time, if the return air falls below 7_C (45_F), the | |
| (DTS) | Controller checks to ensure defrost termination sensor (DTS) has dropped to | |
|
| 10_C or below. If not, a DTS failure alarm is given and the defrost mode is | |
|
| operated off of return temperature sensor (RTS). The defrost mode will be | |
|
| terminated after one hour by the Controller. | |
|
| Alarm 61 is the heater alarm caused by detection of improper amperage resulting | |
AL61 | Heaters Failure | from heater activation (deactivation). Each phase of the power source is checked | |
for proper amperage.This alarm is a display alarm with no resulting failure action, | |||
|
| ||
|
| and will be reset by a proper amp draw of the heater. | |
|
|
| |
|
| Alarm 62 is triggered by improper current draw increase (or decrease) resulting | |
| Compressor Circuit | from compressor turn on (or off). The compressor is expected to draw a minimum | |
AL62 | of 2 amps; failure to do so will activate the alarm.This is a display alarm with no | ||
| Failure | associated failure action and will be reset by a proper amp draw of the | |
|
| compressor. | |
|
|
|