Table 3-1. Controller Configuration Variables

 

 

 

 

 

 

 

 

 

CONFIGURATION

TITLE

DEFAULT

OPTION

 

 

NUMBER

 

 

 

 

 

 

 

1

Bypass Valve Enable

In

Out

 

 

 

 

 

 

 

 

2

Evaporator Fan Speed

dS (Dual)

SS (Single)

 

 

 

 

 

 

 

 

3

Number of Sensor Probes

FoUR

dUAL

 

 

 

 

 

 

 

 

4

Dehumidification Mode

On

Off

 

 

 

 

 

 

 

 

5

Probe Calibration

noCal

CAL

 

 

 

 

 

 

 

 

6

Condenser Fan Speed Select

Off (Single)

On (Variable)

 

 

 

 

 

 

 

 

7

Unit Selection, 20FT/ 40FT/45FT

40ft

20ft,45

 

 

 

 

 

 

 

 

8

Single Phase/Three Phase Motor

1Ph

3Ph

 

 

 

 

 

 

 

 

9

Refrigerant Selection

r134a

r12, r22, bLEnd

 

 

 

 

 

 

 

 

10

Compressor Speed

Out (Single)

In (Dual)

 

 

 

 

 

 

 

 

11

Defrost “Off” Selection

noOFF

OFF

 

 

 

 

 

 

 

 

12

TXV/Solenoid Quench Valve

Out (TXV)

In (Solenoid)

 

 

 

 

 

 

 

 

13

Unloader

Out

In

 

 

 

 

 

 

 

 

14

Condenser Pressure Control (CPC)

In

Out

 

 

 

 

 

 

 

 

15

Discharge Temperature Sensor

Out

In

 

 

 

 

 

 

 

 

16

DataCORDER Option

On (Yes)

Off (No)

 

 

 

 

 

 

 

 

17

Discharge Pressure Sensor

Out (No)

In (Yes)

 

 

 

 

 

 

 

 

18

Heater

Old (Low Watt)

nEW (High Watt)

 

 

 

 

 

 

 

 

19

Controlled Atmosphere

Out (No)

In (Yes)

 

 

 

 

 

 

 

 

20

Pressure Sensor (Suction)

Out (No)

In (Yes)

 

 

 

 

 

 

 

 

21

Auto-Transformer

Std

--

 

 

 

 

 

 

 

 

22

Economy Mode Option

Off

Std, Full

 

 

 

 

 

 

 

 

23

Defrost Interval Timer Save Option

noSAV

SAV

 

 

 

 

 

 

 

 

24

Advanced Pre-Trip Enhanced Test

Off

On

 

 

 

 

 

 

 

 

25

Pre-Trip Test Points/Results Recording

rSLts

data

 

 

3

26

Heat Lockout

Set to --10_C

Set to--5_C

 

 

SECTION

 

 

 

 

 

27

Suction Temperature Display

Out

In

 

 

 

 

 

 

 

 

 

28

Bulb Mode

Nor

bulb

 

 

 

 

 

 

 

 

29

Arctic Mode

Out

In

 

 

 

 

 

 

 

 

30

Compressor Size

41 CFM

37 CFM

 

 

 

 

 

 

 

 

31

Probe Check Logic

Std

SPEC

 

 

 

 

 

 

 

 

32

Single Evaporator Fan Option

2EF0

1EF0

 

 

 

 

 

 

 

 

33

Snap Freeze Option

Off

SnAP

 

 

 

 

 

 

 

 

34

Degree Celsius Lockout Option

bOth

_F

 

 

 

 

 

 

 

 

35

Humidification Mode

Off

On

 

 

 

 

 

 

 

 

36

Modulation Valve Type

1

2, 3

 

 

 

 

 

 

 

 

37

Electronic Partlow

rEtur

SuPPL, bOth

 

 

 

 

 

 

 

 

38

Quench Bypass Valve

Out

In

 

 

 

 

 

 

 

 

39

Current Limit Range

Out

In

 

 

 

 

 

 

 

 

40

Demand Defrost

Out

In

 

 

3-3

T-268-07

Page 41
Image 41
Carrier 69NT40-521, 69NT40-511-199 manual Controller Configuration Variables, Configuration Title Default Option Number