| REMEDY/ | |
CONDITION | POSSIBLE CAUSE | REFERENCE | |
|
| SECTION | |
5.4 UNIT WILL NOT HEAT OR HAS INSUFFICIENT HEATING |
| ||
|
|
| |
| Check | ||
No power to unit | Circuit breaker OFF or defective | Check | |
| External power source OFF | Turn on | |
| Circuit breaker or fuse defective | Replace | |
| Transformer defective (TR) | Replace | |
No control power | Evaporator fan internal motor protector open | 6.15 | |
| Heat relay defective | Check | |
| Heater termination switch open | 6.13 | |
|
|
| |
| Heater(s) defective | 6.14 | |
| Heater contactor or coil defective | Replace | |
| Evaporator fan motor(s) defective or rotating backwards | 6.15/6.16 | |
Unit will not heat or has insufficient | Evaporator fan motor contactor defective | Replace | |
heat | Temperature controller malfunction | 5.9 | |
| Defective wiring | Replace | |
| Loose terminal connections | Tighten | |
| Low line voltage | 2.4 | |
5.5 UNIT WILL NOT TERMINATE HEATING |
| ||
|
|
| |
| Temperature controller improperly set | Reset | |
Unit fails to stop heating | Temperature controller malfunction | 5.9 | |
Heater termination switch remains closed along with the | 6.13 | ||
| |||
| heat relay |
| |
|
|
| |
5.6 UNIT WILL NOT DEFROST PROPERLY |
| ||
|
|
| |
| Defrost timer malfunction | 3.1.4 | |
| Loose terminal connections | Tighten | |
Will not initiate defrost automatically | Defective wiring | Replace | |
Defrost termination sensor defective or heat termination | Replace | ||
| switch open |
| |
| Heater contactor or coil defective | Replace | |
Will not initiate defrost manually | Manual defrost switch defective | Replace | |
Defrost termination sensor open | 4.4.6 | ||
| |||
Initiates but relay (DR) drops out | Low line voltage | 2.4 | |
|
|
| |
Initiates but does not defrost | Heater contactor or coil defective | Replace | |
Heater(s) burned out | 6.14 | ||
| |||
Frequent defrost | Wet load | Normal | |
|
|
|
|