3.3.3DataCORDER Function Codes

There are 35 functions which the operator may access to examine the operating status of the unit. To access these functions, perform the following: Press the ALT. MODE & CODE SELECT keys, press an arrow key

until the left window displays the desired code number (see Table 3-6). The right window will display the value of this item for five seconds before returning to the normal display mode. If a longer time is desired, pressing the ENTER key will extend the time to 30 seconds after the last pressing of the ENTER key.

Table 3-6. DataCORDER Function Code Assignments

NOTE: Inapplicable Functions Display “----------

 

 

 

 

To Access: Press ALT. MODE key

 

 

 

 

 

CODE #

TITLE

 

DESCRIPTION

 

 

 

 

dC1

Recorder Supply

Current recorder supply air temperature.

Temperature

 

 

 

dC2

Recorder Return

Current recorder return air temperature.

Temperature

 

 

 

dC3-5

USDA 1,2,3

Current temperatures of the three USDA probes.

Temperatures

 

 

 

 

Network Sensors

Current values of the network sensors (as configured). Network sensor 1 (Code

dC6-13

6) is generally the humidity sensor and its value is obtained from the Controller

1-8

 

once every minute.

 

 

 

 

 

 

dC14

Cargo Probe 4

Current temperature of the cargo probe #4.

Temperature

 

 

 

dC15-19

Future Expansion

These codes are for future expansion, and are not in use at this time.

 

 

 

 

 

Temperature

Current calibration offset values for each of the five probes: supply, return,

dC20-24

Sensors 1-5

USDA #1, #2, and #3. These values are entered via the interrogation program.

 

Calibration

 

 

 

 

 

 

dC25

Future Expansion

This code is for future expansion, and is not in use at this time..

 

 

 

 

 

The DataCORDER serial number consists of eight characters. Function code

dC26,27

S/N, Left 4, Right 4

dC26 contains the first four characters. Function code dC27 contains the last

four characters. (This serial number is the same as the Controller serial

 

 

 

 

number.)

 

dC28

Minimum Days Left

An approximation of the number of logging days remaining until the

DataCORDER starts to overwrite the existing data.

 

 

dC29

Days Stored

Number of days of data that are currently stored in the DataCORDER.

 

 

 

 

 

The date when a Trip Start was initiated by the user. In addition, if the system

dC30

Date of last Trip start

goes without power for seven continuous days or longer, a trip start will

 

 

automatically be generated on the next AC power up.

 

 

Shows the current status of the optional battery pack.

dC31

Battery Test

PASS -- Battery pack is fully charged.

 

 

FAIL -- Battery pack voltage is low.

dC32

Time: Hour, Minute

Current time on the real time clock (RTC) in the DataCORDER.

 

 

 

dC33

Date: Month, Day

Current date (month and day) on the RTC in the DataCORDER.

 

 

 

dC34

Date: Year

Current year on the RTC in the DataCORDER.

 

 

 

dC35

Cargo Probe 4

Current calibration value for the Cargo Probe. This value is an input via the

Calibration

interrogation program.

 

T-268-07

3-26

Page 64
Image 64
Carrier 69NT40-511-199, 69NT40-521 manual DataCORDER Function Codes, Code # Title Description