the VENT mode is selected on the CA Controller. The user must scroll through the selection by pressing the UP ARROW or DOWN ARROW keys, then pressing the ENTER key when the selection is made. While the tests are being executed, the user can terminate the
The
b. Current Limiting During
Throughout the duration of any
c. Test Codes
A detailed description of the
3.2.1
In this mode, the unit will automatically test unit components using internal measurements and comparison logic, and will provide a “PASS” or “FAIL” display to indicate the results of each test.
If the user depresses the
PRE-TRIP SELECTION MENU
Auto or Auto 1 | Auto 2 (Optional) |
|
|
P, P1, P2, P3, P4, P5, | P, P1, P2, P3, P4, P5, |
P6, rSLts | P6, P7, P8, P9, P10, |
| rSLts |
If the
A given test is selected by pressing ENTER while it is displayed. The entire battery of tests may be run by pressing ENTER while “Auto 1” or “Auto 2” is displayed.
During this selection mode, failure to press either an arrow key or ENTER for five seconds will return the unit to its default display, and normal operating mode.
Any test may be interrupted by pressing the UP ARROW key. This will return the user to the test selection mode described above, and all machinery outputs will be
While certain tests from “Auto 1” are running,
For “Auto 2,” the left display will show
a. Manual Test Operation
Individually selected tests, other than the LED/Display test, will perform the operations necessary to verify the operation of the component under test. At the conclusion of the selected test, PASS or FAIL will be displayed. Upon failure, the Supply and Return LED’s will flash on alternately. This message will remain displayed for up to three minutes, during which time a user may select another test. If the three minute time period expires, the unit will terminate
b. Auto Test Operation From Keypad
If “Auto,” “Auto 1” or “Auto 2” test is initiated, then the unit will execute a series of consecutive tests, each related to an identifiable unit component, without any need for direct user interface. These tests vary in length, depending on the component under test.
When an automatic test fails, it will be repeated once automatically. A repeated test failure will cause “FAIL” to be shown on the right display, with the corresponding test number to the left. The user may then press the DOWN ARROW to repeat the test or the UP ARROW to skip to the next test. The unit will wait indefinitely for user input. Holding the
When “Auto” or “Auto 1” is allowed to run to completion without being interrupted, the unit will exit the
CAUTION
When “Auto 2” is allowed to run to completion without being interrupted, the unit will terminate