STEP
A
Compressor Starting Sequence
*Operating capacity is the required capacity to maintain container box temperature.
**Required voltage is a function of operating capacity and supply frequency.
B
C
YES
D
E
F
G
H
I
J
L
Is Ambient |
|
|
| NO |
| Low Speed |
|
|
|
|
| Run For 2 |
|
|
| |||||||
Temperature Less |
|
|
|
|
|
| Soft Start |
|
|
|
|
| Minutes |
|
|
| ||||||
Than 60 ˚F ? |
|
|
|
|
|
| (See Note A & B) |
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| YES |
|
|
|
|
|
|
| |
High Speed Start |
|
|
|
|
|
|
|
|
|
|
|
| Was Ambient Greater |
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Than 60 ˚F During Start ? |
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| NO |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Does High Pressure |
|
|
|
|
|
|
|
|
|
|
|
| YES |
| Is Supply Voltage |
| ||||||
Switch (HPS) Trip ? |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Greater Than |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Required Voltage ** ? |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| NO |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| NO |
|
|
|
|
| NO |
|
|
|
|
|
| YES |
|
|
|
|
|
|
|
| |||||
Has Compressor Run |
|
|
|
|
|
|
| Are High Speed Switch |
|
|
| |||||||||||
For 20 Minutes ? |
|
|
|
|
|
|
|
|
|
|
|
|
| Over Conditions Satisfied ? |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (Refer To Steps “J & L”) |
|
|
| ||||
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| NO |
|
|
| |
|
| NO |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Has Set Point |
|
|
|
|
|
|
|
|
|
|
|
| Continue In |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Been Reached ? |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Low Speed |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| NO |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Is The Operating Capacity * |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Below Low Speed Capacity ? |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| NOTE A |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Is Supply Voltage | YES |
|
|
|
|
|
|
|
| During |
| compressor |
| |||||||||
Greater Than |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
Required Voltage ** ? |
|
|
|
|
|
|
|
|
|
|
|
|
| operation, if at anytime the |
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| High Pressure Switch (HPS) |
| ||||||
| NO |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| trips, the logic will switch to |
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
Low Speed |
|
|
|
|
|
|
|
|
|
|
|
|
| Low Speed Soft Start. |
|
|
| |||||
Soft Start (See Note B) |
|
|
|
|
|
|
|
|
|
|
|
|
| NOTE B |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Low | Speed | Soft Start | is |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| performed | by closing | the |
| ||||
Run 20 Minutes |
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
| Continue In |
|
|
|
|
| SMV to 0% opening for ten |
| ||||||||||
|
|
|
|
|
|
| Low Speed |
|
|
|
|
| seconds during the |
| ||||||||
|
|
|
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| of the compressor. The SMV |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| opening is | then gradually |
| |||||
Is Supply 3 ˚F Above Set Point | NO |
|
|
|
|
|
| |||||||||||||||
|
|
|
|
|
| increased to the desired value |
| |||||||||||||||
Or Is Operating Capacity * |
|
|
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
| ||||||||||||||
Greater Than Low Speed Capacity ? |
|
|
|
|
|
|
|
| at the rate of a 3% opening |
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| per second. |
|
|
|
|
| ||
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|