When the air temperature decreases to a predetermined tolerance above set point, relay TI energizes and the in-range light is illuminated.

(Refer to section 3.1.4, Code 30.)

If the air temperature continues to fall, modulating cooling starts at approximately 2.5_C (4.5_F) above set point. The modulating valve will have a variable current up to 1.30 amps at full modulation.

During this cooling mode, a running sum of the temperature differential (supply air temperature minus the set point) is kept. When the supply air falls below set point, the differential is negative. The longer supply air remains below set point, the greater the differential in the running sum.

When the supply air temperature decreases to 0.2_C below set point and the running sum is less than -250 degrees C-seconds, relays TN and TC de-energize

shutting off the condenser fan and compressor motors. Also, the cool light is de-energized.

The evaporator fan motors continue to run to circulate air throughout the container. The in-range light remains illuminated as long as the supply air is within a tolerance of set point, and the 15 minute override is met.

If the unit is in the holding mode (neither heating nor cooling) and the supply air temperature increases to 0.2_C (0.4_F) above set point, and providing a six minute off time has elapsed, relay TC energizes to restart the compressor. Also, at this time, the condenser fan motor starts and the cool light is illuminated.

During this mode the dual speed compressor can be either running in high or low speed depending on the box load. Refer to Figure 3-6 for a description of the speed change logic.

T-268-07

4-4

Page 79
Image 79
Carrier 69NT40-511-199, 69NT40-521 manual 268-07