2.10 SUCTION SOLENOID VALVE
The suction solenoid valve, shown in Figure
a. Operation
If set point is below
If set point is above
For both conditions above, at the instant when the SSV opens, the SMV will drop to 20% open, then gradually increase to 100% open. Unless the current limiting suction solenoid overrides or compressor reliability enhancement logic (CREL) restricts its use.
b. Suction Solenoid Override
The suction solenoid override function restricts the opening of the suction solenoid valve (SSV) under certain high ambient and/or box temperature conditions to prevent compressor overload under these high capacity conditions. If the primary return sensor (RTS) fails (alarm code AL56), the suction solenoid valve will not open unless the ambient temperature is less than 10_C (50_F). If the ambient sensor fails (AL57), the suction solenoid valve will not be allowed to open until the return air temperature is less than 1.67_C (35_F). If both the ambient and return air (RTS) sensors fail, the suction solenoid valve will not be allowed to open until at least one of the sensors is repaired.
2.11 REMOTE MONITORING (Optional)
NOTE
The
When the remote monitor plug is connected to the remote monitoring receptacle, the following remote circuits are energized:
CIRCUIT | FUNCTION |
|
|
Sockets B to A | Energizes remote cool light |
|
|
Sockets C to A | Energizes remote defrost light |
|
|
Sockets D to A | Energizes remote |