CODE

#

TITLE

DESCRIPTION

NOTE

Starting with test P7-0 through test P10, these tests are only included with the “Auto2” (Optional) selection menu. (Refer to section 3.2.1.)

 

 

Setup: When the unit is running, the condenser fan is de-energized, and a 15

 

 

minute timer is started. The right display shows discharge pressure if equipped

 

 

with the discharge pressure transducer (DPT), or condenser pressure if

 

 

equipped with a condenser pressure transducer (CPT), or discharge pressure if

 

 

equipped with either a discharge pressure transducer (DPT) or a condenser

 

 

pressure transducer (CPT).

 

 

Pass/Fail Criteria: The test fails if high pressure switch fails to open in 900

 

 

seconds.

 

 

Note, this test is skipped if the unit does NOT have:

 

 

S A compressor discharge sensor (CPDS).

 

 

S A discharge pressure transducer (DPT).

 

 

S Condenser pressure transducer (CPT).

 

 

In addition, this test is skipped if:

 

 

S The sensed ambient temperature is less than 7_C (45_F).

 

 

S The return air temperature is less than -17.8_C (0_F).

 

 

S The water pressure switch (WP) is open, indicating that the unit is

P7-0

High Pressure

operating with a water-cooled condenser.

Switch Closed

Pass/Fail Criteria: Under conditions of the above Note, the test immediately

 

 

 

fails if the following inputs are sensed to be invalid:

 

 

S Compressor discharge sensor (CPDS).

 

 

S Discharge pressure transducer (DPT).

 

 

S Condenser pressure transducer (CPT).

 

 

OR if any one of the following inputs are sensed to be invalid:

 

 

S Return temperature sensor (RTS).

 

 

S Ambient sensor (AMBS).

 

 

In addition, the test will fail if:

 

 

S The high pressure switch (HPS) fails to open within 15 minutes.

 

 

S The discharge temperature exceeds 138_C (280_F).

 

 

S The discharge temperature is less than or equal to ambient temperature

 

 

plus 5_C (9_F).

 

 

S The condenser pressure transducer (CPT) or discharge pressure

 

 

transducer (DPT) pressure exceeds 27.42 kg/cm2 (390 psig).

 

 

Requirements: Test P7-0 must pass for this test to execute. Setup: The

P7-1

High Pressure

condenser fan is started and a 60 second timer is started.

Switch Open

Pass/Fail Criteria: Passes the test if the high pressure switch (HPS) closes

 

 

 

within the 60 second time limit, otherwise, it fails.

 

 

 

 

 

Setup: If the container temperature is below 60_F, the set point is changed to

 

 

60_F, and a 60 minute timer is started. The left display will read “P8-0.” The

P8-0

Perishable Mode

control will then heat the container until 60_F is reached. If the container

temperature is above 60_F at the start of the test, then the test proceeds

Heat Test

 

immediately to test P8-1 and the left display will change to “P8-1.”

 

 

 

 

Pass/Fail Criteria: The test fails if the 180 minute timer expires before the

 

 

control temperature reaches set point. The display will read “P8--0,” “FAIL.”

T-268-07

3-22

Page 60
Image 60
Carrier 69NT40-511-199, 69NT40-521 manual Addition, this test is skipped if, Addition, the test will fail if