STEP

A

B

C

D

E

Compressor Starting Sequence

Is Ambient

Temperature Less

Than 60 ˚F ?

YES

High Speed Start

Has Set Point Been Reached ?

NO

Continue In

High Speed

NO

Low Speed

Has Set Point

 

Soft Start

Been Reached ?

 

(See Note A & B)

 

 

 

NO

 

 

Run For 2

 

 

Minutes

YES

Compressor Cycles OFF

YES

 

NOTE A

 

During

compressor

 

operation, if at anytime the

 

High Pressure Switch (HPS)

 

trips, the logic will switch to

 

3

Low Speed Soft Start.

SECTION

 

 

 

 

 

NOTE B

Low Speed Soft Start is performed by closing the SMV to 0% opening for ten seconds during the start-up of the compressor. The SMV opening is then gradually increased to the desired value at the rate of a 3% opening per second.

Figure 3-7. Two-Speed Compressor Speed Change Logic -- Frozen Range Only

3-37

T-268-07

Page 75
Image 75
Carrier 69NT40-511-199, 69NT40-521 manual Compressor Cycles OFF