3.2.2Pre-Trip Mode
At the end of the
|
| Table | |
|
|
| |
CODE | TITLE | DESCRIPTION | |
# | |||
|
| ||
|
| NOTE |
“Auto” or “Auto1” menu includes the following: P, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2’ (Optional)
menu includes the following: P, P1, P2, P3, P4, P5, P6,P7, P8, P9, P10 and rSLts. (Refer to section 3.2.1.)
|
| All lights and display segments will be energized for five seconds at the start of | |
P | the | ||
|
| no test codes or results associated with this phase of | |
|
|
| |
|
| Setup: Heater must start in the OFF condition, and then be turned on. A current | |
Heaters Turned On | draw test is done after 15 seconds. | ||
Pass/Fail Criteria: Passes if change in current draw is within the range | |||
|
| ||
|
| specified. | |
|
|
| |
|
| Setup: Heater must start in the ON condition, and then be turned off. A current | |
Heaters Turned Off | draw test is done after 10 seconds. | ||
Pass/Fail Criteria: Passes if change in current draw is within the range | |||
|
| ||
|
| specified. | |
|
| Requirements: Water pressure switch (WP) input must be closed. | |
|
| Setup: Condenser fan is turned ON, a current draw test is done after 15 | |
Condenser Fan On | seconds. | ||
|
| Pass/Fail Criteria: Passes if change in current draw test is within the range | |
|
| specified. | |
|
| Setup: Condenser fan is turned OFF, a current draw test is done after 10 | |
Condenser Fan Off | seconds. | ||
Pass/Fail Criteria: Passes if change in current draw test is within the range | |||
|
| ||
|
| specified. | |
|
|
| |
|
| Requirements: The unit must be equipped with a low speed evaporator fan, as | |
| Low Speed | determined by the Evaporator Fan speed select configuration variable. | |
P3 | NOTE: If the unit is configured for single evaporator fan operation, | ||
Evaporator Fans | |||
| |||
|
| ||
|
| AL12 are active at the start of testing. | |
|
|
| |
|
| Setup: The high speed evaporator fans will be turned on for 10 seconds, then off | |
| Low Speed | for two seconds, then the low speed evaporator fans are turned on. A current | |
Evaporator Fan | draw test is done after 60 seconds. | ||
| Motors On | Pass/Fail Criteria: Passes if change in current draw is within the range | |
|
| specified. Fails if AL11 or AL12 activates during test. | |
|
|
| |
| Low Speed | Setup: The low speed Evaporator Fan is turned off, a current draw test is done | |
| after 10 seconds. | ||
Evaporator Fan | |||
Pass/Fail Criteria: Passes if change in current draw is within the range | |||
| Motors Off | ||
| specified. Fails if AL11 or AL12 activates during test. | ||
|
| ||
| High Speed | Setup: The high speed Evaporator Fan is turned on, a current draw test is done | |
| after 60 seconds. | ||
Evaporator Fan | |||
Pass/Fail Criteria: Passes if change in current draw is within the range | |||
| Motors On | ||
| specified. Fails if AL11 or AL12 activates during test. | ||
|
|