c. Auto Test Operation From Serial

d. Pre-Trip Test Results

Communications

 

Pre-trip may also be initiated via communications. The operation is the same as for the Auto Test mode described above except that should a test fail, the pre-trip mode will automatically terminate. When initiated via communications, a test may not be interrupted with an arrow key, but the pre-trip mode can be terminated with the PRE-TRIP key.

3.2.2Pre-Trip Mode

At the end of the pre-trip test selection menu, the message “P,” “rSLts” will be displayed. Pressing the ENTER key will allow the user to see the results for all subtests (i.e., 1-0, 1-1, etc). The results will be displayed as “PASS” or “FAIL” for all the tests run to completion since power up. If a test has not been run since power up, “--------” will be displayed.

 

 

Table 3-5. Pre-Trip Test Codes

 

 

 

CODE

TITLE

DESCRIPTION

#

 

 

 

 

NOTE

“Auto” or “Auto1” menu includes the following: P, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2’ (Optional)

menu includes the following: P, P1, P2, P3, P4, P5, P6,P7, P8, P9, P10 and rSLts. (Refer to section 3.2.1.)

 

 

All lights and display segments will be energized for five seconds at the start of

P

Pre-Trip Initiated

the pre-trip. Since the unit cannot recognize lights and display failures, there are

 

 

no test codes or results associated with this phase of pre-trip.

 

 

 

 

 

Setup: Heater must start in the OFF condition, and then be turned on. A current

P1-0

Heaters Turned On

draw test is done after 15 seconds.

Pass/Fail Criteria: Passes if change in current draw is within the range

 

 

 

 

specified.

 

 

 

 

 

Setup: Heater must start in the ON condition, and then be turned off. A current

P1-1

Heaters Turned Off

draw test is done after 10 seconds.

Pass/Fail Criteria: Passes if change in current draw is within the range

 

 

 

 

specified.

 

 

Requirements: Water pressure switch (WP) input must be closed.

 

 

Setup: Condenser fan is turned ON, a current draw test is done after 15

P2-0

Condenser Fan On

seconds.

 

 

Pass/Fail Criteria: Passes if change in current draw test is within the range

 

 

specified.

 

 

Setup: Condenser fan is turned OFF, a current draw test is done after 10

P2-1

Condenser Fan Off

seconds.

Pass/Fail Criteria: Passes if change in current draw test is within the range

 

 

 

 

specified.

 

 

 

 

 

Requirements: The unit must be equipped with a low speed evaporator fan, as

 

Low Speed

determined by the Evaporator Fan speed select configuration variable.

P3

NOTE: If the unit is configured for single evaporator fan operation, Pre-Trip tests

Evaporator Fans

 

P3-0, P3-1, P4-0 and P4-1 will fail immediately if Controller alarm codes AL11 or

 

 

 

 

AL12 are active at the start of testing.

 

 

 

 

 

Setup: The high speed evaporator fans will be turned on for 10 seconds, then off

 

Low Speed

for two seconds, then the low speed evaporator fans are turned on. A current

P3-0

Evaporator Fan

draw test is done after 60 seconds.

 

Motors On

Pass/Fail Criteria: Passes if change in current draw is within the range

 

 

specified. Fails if AL11 or AL12 activates during test.

 

 

 

 

Low Speed

Setup: The low speed Evaporator Fan is turned off, a current draw test is done

 

after 10 seconds.

P3-1

Evaporator Fan

Pass/Fail Criteria: Passes if change in current draw is within the range

 

Motors Off

 

specified. Fails if AL11 or AL12 activates during test.

 

 

 

High Speed

Setup: The high speed Evaporator Fan is turned on, a current draw test is done

 

after 60 seconds.

P4-0

Evaporator Fan

Pass/Fail Criteria: Passes if change in current draw is within the range

 

Motors On

 

specified. Fails if AL11 or AL12 activates during test.

 

 

SECTION 3

3-19

T-268-07

Page 57
Image 57