Carrier 69NT40-511-199, 69NT40-521 manual Unit Runs but has Insufficient Cooling

Models: 69NT40-521 69NT40-511-1 69NT40-511-199

1 138
Download 138 pages 33.05 Kb
Page 91
Image 91

SECTION 5

TROUBLESHOOTING

 

 

REMEDY/

 

CONDITION

POSSIBLE CAUSE

REFERENCE

 

 

 

SECTION

 

5.1 UNIT WILL NOT START OR STARTS THEN STOPS

 

 

 

 

 

 

 

External power source OFF

Turn on

 

No power to unit

Start-Stop switch OFF or defective

Check

 

Circuit breaker tripped or OFF

Check

 

 

 

 

Modular transformer not connected

6.22

 

 

 

 

 

Loss of control power Loss of

Circuit breaker OFF or defective

Check

 

Control transformer (TR) defective

Replace

 

control power in respective branch

 

Fuse (F3) blown

Check

 

of control circuit only

 

Start-Stop switch OFF or defective

Check

 

 

 

 

 

 

 

 

Evaporator fan motor internal protector open

6.15

 

Loss of control power in respective

Condenser fan motor internal protector open

6.18

 

Compressor internal protector open

6.7

 

branch of control circuit only

 

High pressure switch open

5.7

 

 

 

 

Heat termination thermostat (HTT) open

Replace

 

 

 

 

 

 

Low line voltage

Check

 

 

Single phasing

Check

 

Compressor hums, but does not

Shorted or grounded motor windings

6.7

 

start

Compressor seized

6.7

 

 

Contactor (SC) shorting (in high speed mode of two-speed

Check

 

 

compressor only)

 

 

Compressor will occasionally

Compressor speed change (On units with two-speed

Normal

 

de-energize for 15 seconds

compressor)

 

 

5.2 UNIT RUNS BUT HAS INSUFFICIENT COOLING

 

 

 

 

 

 

Compressor

Compressor valves defective

6.7

 

 

 

 

 

 

Abnormal pressures

5.7

 

 

Temperature controller malfunction

5.9

 

Refrigeration System

Evaporator fan or motor defective

6.15

 

Suction modulation valve malfunction

6.25

 

 

Suction solenoid valve malfunction

2.10/6.24

 

 

Condenser Pressure Transducer (CPT) defective

Check

 

 

Shortage of refrigerant

6.6

 

5.3 UNIT OPERATES LONG OR CONTINUOUSLY IN COOLING

 

 

 

 

 

 

Container

Hot load

Normal

 

Defective box insulation or air leak

Repair

 

 

 

 

Shortage of refrigerant

6.4/6.6

 

 

Evaporator coil covered with ice

5.6

5

 

Evaporator coil plugged with debris

6.13

 

SECTION

 

Evaporator fan(s) rotating backwards

6.15/6.16

 

 

 

Defective evaporator fan motor/capacitor

6.15/6.16

 

 

Air bypass around evaporator coil

Check

 

Refrigeration System

Controller set too low

Reset

 

 

Compressor service valves or liquid line shutoff valve

Open valves

 

 

partially closed

completely

 

 

Dirty condenser

6.17

 

 

Compressor worn

6.7

 

 

Current limit (Code 32) set to wrong value

3.1.4

 

 

Suction modulation valve (SMV) malfunction

6.25

 

5-1

T-268-07

Page 91
Image 91
Carrier 69NT40-511-199 manual Unit Runs but has Insufficient Cooling, Unit Operates Long or Continuously in Cooling