4.2 STARTING AND STOPPING INSTRUCTIONS
CAUTION
Make sure that the unit circuit breaker(s)
a. Starting the Unit
NOTE
The evaporator fans will always start in high speed regardless of set point and will switch to low speed after approximately 20 to 30 seconds if the set point is below
1.Refer to
2.Check power source for proper voltage. Connect unit power plug and turn main power ON.
3.Turn refrigeration unit circuit breaker(s), and the
4.Units equipped with the integrated DataCORDER:
Trip start is initiated by depressing the ALT. MODE key and selecting Code dc30, then depressing the ENTER key for five seconds.
5.Refer to section 4.3 after unit is running.
b. Stopping the Unit
Turn the
4.3 AFTER STARTING INSPECTION
a.Check rotation of condenser and evaporator fans.
b.Check compressor oil level. (Refer to section 6.10.)
c.Run unit at least five minutes to stabilize. Start controller
(Refer to section 3.2.)
4.4 UNIT OPERATION
4.4.1Crankcase Heater
When the crankcase heater is installed, it will be operational whenever the compressor is off and there is power to the unit. The heater is connected to a set of normally closed auxiliary contacts on the compressor contactor (CH).
4.4.2Probe Check Initiation
Whenever the unit is in normal control mode, that is, not in
The following is based on current ML2i operational software logic, version 5103. Older versions of software will have differences.
a. Probe Diagnostic Logic
If the unit is configured for standard (Std) “Probe Check Logic,” the criteria used for comparison between the primary and secondary control probes is:
S1_C (1.8_F) for perishable set points, above
S2_C (3.6_F) for frozen set points, below above range.
SIf 25 or more of 30 readings taken within a 30 minute period are
b.Special
If the unit is configured for special (SPEC) “Probe Check Logic,” the above criteria is identical except for the diagnostic readings which are:
SIf 25 or more of 30 readings taken within a 30 minute period OR any 10 consecutive readings at any time are
*The only time defrost will not be initiated is if the defrost termination sensor (DTS) is greater than 25.56_C (78_F).
The 30 minute timer will be reset for each of the following conditions:
SAt every power up.
SAt the end of every defrost.
SAfter every diagnostic check that does not fall outside of the limits as described under “standard or special” as outlined above.