4.4.5Heating (See Figure 4-4.)
The unit will heat only when the controller set point is above
If the air temperature decreases 0.5_C (0.9_F) below controller set point, TH closes and the system enters the heating mode which is designed to raise the container air temperature. When TH closes, power flows through TH contacts and the heat termination thermostat to energize the heat contactor (HR). This in turn energizes the heaters and heat light. The evaporator fans continue to run to circulate air throughout the container.
As the supply air decreases to the
When the temperature rises to 0.2_C (0.4_F) below set point, TH opens (heating off) and the system again enters the holding zone. The compressor and condenser fan motor are not running as contactors CH and CF remain
A safety heater termination thermostat (HTT) attached to an evaporator coil support, set to open at 54.5_C (130_F), will open the heating circuit if overheating occurs.
|