Carrier 69NT40-521, 69NT40-511-199 manual Code Title Description

Models: 69NT40-521 69NT40-511-1 69NT40-511-199

1 138
Download 138 pages 33.05 Kb
Page 47
Image 47

CODE

TITLE

DESCRIPTION

 

 

#

 

 

 

 

 

 

 

 

Inapplicable Functions Display ----------

 

 

 

 

The current limit is the maximum current demand allowed on any phase at any

 

 

 

 

time. Limiting the unit’s current (amperage) reduces the load on the main power

 

 

Cd32

Current Limit

and lowers the compressor discharge pressure. When desirable, the limit can be

 

 

 

(Amperes)

lowered. Note, however, that capacity is also reduced. The five values for 460vac

 

 

 

 

operation are:

 

 

 

 

15, 17, 19, 21 (Factory Default), 23

 

 

 

 

This code is only applicable to units with a humidity sensor (HS).Relative humidity

 

 

 

 

set point is available only on units configured for dehumidification. When the

 

 

 

 

mode is activated, the control probe LED flashes on and off every second to alert

 

 

 

 

the user. If not configured, the mode is permanently deactivated and Cd33 will

 

 

 

Dehumidification

display “----------.” When set point is available, it can be set to “OFF.” “TEST,” or 65

 

 

Cd33

Control (% RH)

to 95% relative humidity in increments of 1%. If bulb mode is active (code Cd35)

 

 

 

(Optional)

and “Lo” speed evaporator motors are selected (code Cd36) then set point

 

 

 

 

ranges from 60 to 95%. When “TEST” is selected or test set point is entered, the

 

 

 

 

heaters should be turned on, indicating that dehumidification mode is activated.

 

 

 

 

After a period of five minutes has elapsed in this mode, the previously selected

 

 

 

 

mode is reinstated.

 

 

 

Economy Mode

Economy mode is a user selectable mode of operation provided for power saving

 

 

Cd34

purposes. Refer to sections 3.1.7.1 and 3.1.7.2 for a more detailed description of

 

 

 

(On--Off) (Optional)

economy mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

Bulb mode is a user selectable mode of operation that is an extension of normal

 

 

 

Bulb Mode

dehumidification. If dehumidification is set to “Off,” code Cd35 will display “Nor”

 

 

 

and the user will be unable to change it. After a dehumidification set point has

 

 

Cd35

(Normal--Bulb)

 

 

been selected and entered for code Cd33, the user may then change code Cd35

 

 

 

(Optional)

 

 

 

to “bulb.” After bulb has been selected and entered, the user may then utilize

 

 

 

 

 

 

 

 

function codes Cd36 and Cd37 to make the desired changes.

 

 

 

 

 

 

 

 

 

This code is enabled only if a dehumidification set point has been selected using

 

 

 

 

function code Cd33 and “bulb” has been selected using function code Cd35. If

 

 

 

Evaporator Speed

these conditions are not met, “alt” will be displayed indicating that the evaporator

 

 

 

fans will alternate their speed whenever a dehumidification set point is selected.

 

 

 

Select

 

 

Cd36

This display cannot be changed by the user. If a dehumidification set point has

 

 

 

(Cd35 must be in

been selected along with bulb mode then “alt” may be selected for alternating

 

 

 

 

 

 

“Bulb”)

 

3

 

speed, “Lo” for low speed evaporator fan only, or “Hi” for high speed evaporator

 

 

 

 

SECTION

 

 

fan only. If a setting other than “alt” has been selected and bulb mode is

 

 

 

 

 

 

 

deactivated in any manner, then selection reverts back to “alt.”

 

 

 

 

 

 

 

 

 

This code, as with function code Cd36, is used in conjunction with bulb mode and

 

 

 

 

dehumidification. If bulb mode is active, this code allows the user to change the

 

 

 

Defrost Temperature

temperature above which the defrost termination sensor (DTS) temperature must

 

 

Cd37

go to terminate defrost. It allows the user to change the setting from 4_C to

 

 

Sensor Setting

25.6_C in 0.1_C (0.2_F) increments. This value is changed using the UP/DOWN

 

 

 

(Optional)

 

 

 

ARROW keys, followed by the ENTER key when the desired value is displayed. If

 

 

 

 

 

 

 

 

bulb mode is deactivated in any manner, the DTS setting above which defrost

 

 

 

 

terminates defaults to the normal 25.6_C (78_F) setting.

 

 

 

 

 

 

 

 

 

NOTE

 

 

In the unlikely event that AL55 activates, Function Codes Cd38 and Cd39 will display SRS and RRS,

 

 

respectively.

 

 

 

 

 

This code is only applicable to units without a DataCORDER that are configured

 

 

 

Secondary Supply

to have four probes. If this is true, it will then display the current secondary supply

 

 

Cd38

Air Temperature

air temperature.If the unit is configured with a DataCORDER, the Controller

 

 

 

(Optional)

function code Cd38 will display “----------.” and the display values for SRS will

 

 

 

 

appear on the DataCORDER function code dC1.

 

 

 

 

 

 

 

3-9

T-268-07