Chapter 6 - Hardware Reference

Step, Direction, and Shutdown Inputs

Application Notes:

1.When wiring TTL signals to other manufacturer’s indexers, the Step TTL command signals from the controller should be wired to Step +, the Direction signal to Dir +, and the Shutdown signal to SD + (Step -, Dir -,and SD - should not be connected). Remember to connect commons.

2.Activating the Shutdown input (logic low) disables the drive amplifier and de-energizes the motor. When this input is off (logic high) the drive is enabled and the motor is energized.

COM 237

2.2n 50V COM

4.99K

 

 

 

+5V

 

4.99K

 

 

STEP-

 

 

 

 

 

 

DIR-

 

 

 

 

 

 

 

 

 

 

 

 

SD-

4.99K

STEP+, DIR+, SD+

SINKING

COM OUTPUT

COM

Impulse internal

external

Single-Ended

Installation

 

4.99K

4.99K +5V

 

STEP-

DIFFERENTIAL

COM

 

 

 

DIR-

 

 

 

DRIVER

237

 

 

 

SD-

 

4.99K

 

 

 

 

 

 

2.2n 50V

 

 

 

 

AM26LS32

 

STEP+

 

 

 

COM

 

 

 

 

 

 

 

 

 

DIR+

 

 

 

 

 

 

 

 

 

 

SD+

 

 

 

Impulse internal

 

external

 

Differential Installation

Fault Output

+5V

 

FAULT+

EQUIVALENT

 

4N35

CIRCUITS

 

 

 

 

 

237

 

 

 

 

 

 

NC

 

 

 

 

Drive Faulted

 

 

 

 

FAULT+

FAULT-

FAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No Fault Present

 

 

 

 

 

 

 

 

FAULT-

FAULT+

FAULT-

 

Impulse internal

 

external

 

 

 

 

 

 

 

 

 

6-5

Page 81
Image 81
Impulse PCW-5181 Step, Direction, and Shutdown Inputs, Fault Output, Application Notes, Single-Ended Installation