APPENDIX D Preparing Your Site
•The distance between the mounting holes in the two posts must be 18.31 inches ±.063 inch, as specified in the EIA 310-C.
•Do not use an enclosed rack for the ERX-700 series. It does not provide adequate ventilation.
•A fully loaded rack with three ERX-1400 series systems must structurally support 300 pounds (136 kilograms).
•The system fits in a 19-inch rack. You can install a system in a 23-inch rack if you use the 23-inch ears available from Juniper Networks. Contact your Juniper Networks sales representative for more information.
Space Requirements
If you use an enclosed rack for an ERX-1400 series system, ensure that there is a minimum of 3 inches of clearance between the inner side wall and the system. This clearance space will allow adequate air flow.