Complete Hardware Guide for EX2200 Ethernet Switches
•If you are mounting an EX2200 switch in a rack or cabinet with other equipment, or if you are placing it on the desktop or floor near other equipment, ensure that the exhaust from other equipment does not blow into the intake vents of the chassis.
•Leave at least 24 in. (61 cm) in front of the switch and 6 in. (15.2 cm) behind the switch. For service personnel to remove and install hardware components, you must leave adequate space at the front and back of the switch. NEBS
Related • Rack Requirements for EX2200 Switches on page 39
Documentation
• Cabinet Requirements for EX2200 Switches on page 40
• General Site Guidelines for EX Series Switches on page 35
•
• Cooling System and Airflow in an EX2200 Switch on page 15