Page 48 of 332 Chapter 3 — System and site requirements

The following are additional grounding requirements:

CAUTION

Never connect the single point ground conductor from the Option 11C Mini system to structural steel members or electrical conduit. Never tie this conductor to a ground source or grounded electrode that is not hard-wired to the building reference conductor.

Ground conductors for the Option 11C Mini system:

must not be smaller than #6 AWG (#40 metric) at any point (see Table 10 on page 49. This table provides a list of grounding wire requirements specific to some areas)

must be routed through the same conduit as the phase conductors that serve the system

must not be smaller than any phase conductor in the same conduit

do not carry current under normal operating conditions

All ground conductors in the building:

must be isolated from the neutral bus except at the service entrance to the building

must be hardwired to the main ground reference

Avoid spliced conductors. Continuous conductors have lower impedance, and they are more reliable than spliced conductors.