Chapter 8 — Bracing the Option 11C Mini against earthquakes

Page 107 of 332

 

 

Table 23 provides the hardware recommendations for earthquake bracing.

Table 23

Hardware recommendations

 

 

 

 

 

 

Minimum depth

Suggested

 

 

 

 

Vertical spacing

 

fasteners must

Type of wall

Fastener

 

screw

between fasteners

 

be embedded in

 

 

 

 

 

length

 

 

 

 

 

 

the wall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wood stud

#10 Wood Screws

16 in. (400 mm) on center

1 in. (25 mm)

2 in. (50 mm)

Metal stud

#14 Sheet Metal

16 in. (400 mm) on center

 

1.5 in. (37.5

 

Screws

 

 

 

mm)

Concrete

1/4 in. (6 mm) Hilti

24 in. (600 mm) on center

1 1/8 in. (28 mm)

2 in. (50 mm)

 

KB-II

 

 

 

 

 

 

Masonry

1/4 in. (6 mm)

24 in. (600 mm) on center

 

2 in. (50 mm)

 

Ramset Redhead

 

 

 

 

 

 

Dynabolt Sleeve

 

 

 

 

 

 

Anchor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 24 lists the maximum sizes of wall studs with a 16-inch spacing.

 

 

Table 24

 

 

 

 

 

 

 

Maximum wall stud sizes — 16 inch spacing

 

 

 

 

 

 

 

 

 

 

 

 

Wall Studs

 

Maximum Height of wall

 

 

 

 

 

 

 

 

 

 

 

Wood Studs

 

 

 

 

 

 

 

2

X 4 (DF #2)

 

11 ft (3300 mm)

 

 

 

 

2

X 6 (DF #2)

 

19 ft (5700 mm)

 

 

 

 

Metal Studs

 

 

 

 

 

 

 

2

1/2 X 20 Gauge

9 ft

(2700 mm)

 

 

 

 

2

1/2 X 16 Gauge

10 ft (3000 mm)

 

 

 

 

2

1/2 X 14 Gauge

11 ft (3300 mm)

 

 

 

 

3

5/8 X 20 Gauge

12 ft (3600 mm)

 

 

 

 

3

5/8 X 18 Gauge

13 ft (3900 mm)

 

 

 

 

3

5/8 X 16 Gauge

14 ft (4200 mm)

 

 

 

 

3

5/8 X 14 Gauge

16 ft (4800 mm)

 

 

 

 

4

X 20 Gauge

 

14 ft (4200 mm)

 

 

 

 

4

X 18 Gauge

 

15 ft (4500 mm)

 

 

 

 

 

 

 

 

 

 

 

Option 11C Mini Planning and Installation Guide

Page 107
Image 107
Nortel Networks manual Bracing the Option 11C Mini against earthquakes, Metal Studs