Page 180 of 332 Chapter 13 — Installing and connecting the cross-connect terminal

3Tighten the velcro straps when you have connected each cable to the chassis.

4For systems required to meet CISPR-B Electromagnetic Compatibility (EMC), perform the following step. On each installed 25-pair cable, attach the supplied ferrite filter to the cable. Attach the ferrite filter as near the connector as possible (see Figure 53). To attach the ferrite filter, press the cable firmly into the groove on one side of the open filter. Close the filter around the cable and press the filter together using the fastening clip snaps close.

Figure 53

A ferrite filter installed on a 25-pair cable (CISPR-B EMC systems)

25-pair cable to cross-connect terminal

Ferrite filter

5Terminate all the 25-pair cables installed at the cross-connect terminal.

Label all the cables at the cross-connect terminal blocks according to the card slot assignment plan.

6Install the AUX cable in the lower 9-pin connector located on the bottom left-hand side of the Main Chassis. See Figure 54.

553-3021-209 Standard 3.00 April 2000

Page 180