Chapter 3 — System and site requirements

Page 49 of 332

 

 

All conductors must terminate in a permanent way. Make sure all terminations are easily visible and available for maintenance purposes.

Tag ground connections with a clear message such as “CRITICAL CONNECTION: DO NOT REMOVE OR DISCONNECT”.

Table 10

Area-specific grounding wire requirements

Area

Grounding wire requirements

 

 

Germany

#8 AWG (10 mm2) green/yellow wire

Other areas in Europe

not smaller than #6 AWG (16 mm2) at any

 

point

UK

two green/yellow wires no thinner than two

 

10 mm2

CAUTION

For an installed Option 11C Mini, the impedance of the link between the ground post of the Main Chassis and the single point ground to which it connects must be less than 0.25 Ohms.

CAUTION

Transients in supply conductors and ground systems can damage integrated circuits. This damage can result in unreliable Option 11C Mini operation. Damage caused by transients is not always immediately apparent. Degradation can occur over a period of time.