Chapter 11 – Installing the system ground

This chapter describes how to ground the Option 11C Mini chassis. This chapter contains the following procedures:

Procedure 7: “Grounding the Option 11C Mini chassis” on page 141

Procedure 8: “UK grounding procedure for the Option 11C Mini chassis” on page 144

This chapter also describes how to ground multiple pieces of equipment in a rack/cabinet when one or more pieces of equipment does not have a grounding lug. See “Grounding multiple pieces of equipment in a rack/cabinet” on page 144.

Refer to the “Grounding requirements” on page 47 for additional information.

WARNING

Correct grounding is very important. Failure to complete the grounding procedures may result in a system that is unsafe for the personnel using the equipment. If your system is not grounded correctly, it may not be protected from lighting or power surges, and it may be subject to service interruptions.

You must use insulated ground wire for system grounding.

Chassis powered by the same service panel

For each Main Chassis, connect a #6 AWG (#40 Metric Wire Gauge) ground wire from the Main Chassis to an NTBK80 grounding block. Connect the grounding block to a ground source (the ground bus in the AC service panel).

Option 11C Mini Planning and Installation Guide

Page 139