10.3.7Using the UPM EMERGENCY UPM OFF Pushbutton
NOTE: The UPM EMERGENCY UPM OFF pushbutton will only interrupt the ability for that module to deliver power to the critical bus. The redundant modules continue to support the critical load.
Emergency UPM shutdown is initiated by the covered, red UPM EMERGENCY UPM OFF pushbutton on the UPM Monitor Panel. This pushbutton is protected by a clear plastic shield to prevent accidental activation. In an emergency, you can press this pushbutton to instantaneously open all UPM breakers and interrupt UPM output. The UPM remains locked off until you reset the EMERGENCY UPM OFF pushbutton.
To restart the UPS after pressing the EMERGENCY UPM OFF pushbutton, follow the procedure “Resetting the UPM after Shutdown” of this chapter before starting the UPS.
NOTE: The UPM REMOTE EMERGENCY LOAD OFF (REPO) functions in the same way as the UPM EMERGENCY UPM OFF pushbutton on the UPM Monitor panel.
10.3.8To Use the UPM EMERGENCY UPM OFF Pushbutton
1.Raise the clear plastic shield covering the red EMERGENCY UPM OFF pushbutton on the UPM Monitor Panel.
2.Press the EMERGENCY UPM OFF pushbutton.
UPS breakers CB1 and CB3 and Battery breaker CB2 (MBB) open. The EMERGENCY UPM OFF PUSH TO RESET pushbutton on the UPM Control Panel pops out. The UPM shuts down.
10.3.9Resetting the UPM after an EMERGENCY UPM Shutdown
CAUTION:
Do not attempt to restart the UPM after Emergency UPM Shutdown until the
cause of the emergency has been identified and cleared.
The EMERGENCY UPM OFF PUSH TO RESET pushbutton is a small white button on the UPM Control Panel. The PUSH TO RESET pushbutton pops out when the EMERGENCY UPM OFF pushbutton on the Monitor Panel is activated.
To reset the UPM:
1.Press the EMERGENCY UPM OFF PUSH TO RESET pushbutton until it clicks in and remains recessed.
2.The UPM is now reset. To restart the UPM, follow the procedure in this chapter, “Restarting a Single UPM.”
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM | |
| 164201373 Rev. A 092402 |