12.The 100% rated bypass input overcurrent protection and bypass input disconnect switch are to be provided by the user. Table E lists the maximum rating for output circuit breakers satisfying the criteria for both. Rating is based on 100% of output current for a 100% breaker.
Table E. Maximum Bypass Input Circuit Breaker Ratings
Powerware 9315 Switchboard System Bypass module |
| SSBM Model |
| ||
2500 |
| 3000 |
| 4000 | |
|
|
| |||
SSBM Bypass | 2500 |
| 3000 |
| 4000 |
SMB Bypass | 2500 |
| 3000 |
| 4000 |
13.The breakers CBS, CBP, FBP, MBP (optional) and MIS (optional) have AT trip ratings and a maximum Amp Interrupting Capability (KAIC) as shown in Table F.
Table F. SSBM Breaker Trip Ratings and Amp Interrupting Capability
Powerware 9315 Switchboard System Bypass |
|
|
|
| SSBM Model |
| |
2500 |
| 3000 |
| 4000 |
| All Models | |
module |
|
|
| ||||
| Trip Rating |
|
| KAIC | |||
|
|
|
| ||||
SSBM and SMB | N/A |
| 3000 |
| 4000 |
| 65 |
2500 |
| 3000 |
| 4000 |
| 100 | |
|
|
|
|
14.The 100% rated output overcurrent protection and output disconnect switch are to be provided by the user. Table G lists the maximum rating for output circuit breakers satisfying the criteria for both. Rating is based on 100% of output current for a 100% breaker.
Table G. Maximum Output Circuit Breaker Ratings
Powerware 9315 Switchboard System Bypass module |
| SSBM Model |
| ||
2500 |
| 3000 |
| 4000 | |
|
|
| |||
SSBM | 2500 |
| 3000 |
| 4000 |
SMB | 2500 |
| 3000 |
| 4000 |
15.In the Parallel Capacity/Redundant System, each UPS module, Switchboard System Bypass Module (SSBM), SSBM breakers, and optional equipment are crated separately for shipping.
16.Do not tilt cabinets more than ¦10˚during handling.
17.Dimensions are in millimeters (inches).
DESCRIPTION:
INSTALLATION NOTES
DRAWING NO: | |
|
SHEET: 5 of 6
|
|
|
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM | ||
| 164201373 Rev. A 092402 |