12.The 100% rated bypass input overcurrent protection and bypass input disconnect switch are to be provided by the user. Table E lists the maximum rating for output circuit breakers satisfying the criteria for both. Rating is based on 100% of output current for a 100% breaker.

Table E. Maximum Bypass Input Circuit Breaker Ratings

Powerware 9315 Switchboard System Bypass module

 

SSBM Model

 

2500

 

3000

 

4000

 

 

 

SSBM Bypass

2500

 

3000

 

4000

SMB Bypass

2500

 

3000

 

4000

13.The breakers CBS, CBP, FBP, MBP (optional) and MIS (optional) have AT trip ratings and a maximum Amp Interrupting Capability (KAIC) as shown in Table F.

Table F. SSBM Breaker Trip Ratings and Amp Interrupting Capability

Powerware 9315 Switchboard System Bypass

 

 

 

 

SSBM Model

 

2500

 

3000

 

4000

 

All Models

module

 

 

 

 

Trip Rating

 

 

KAIC

 

 

 

 

SSBM and SMB

N/A

 

3000

 

4000

 

65

2500

 

3000

 

4000

 

100

 

 

 

 

14.The 100% rated output overcurrent protection and output disconnect switch are to be provided by the user. Table G lists the maximum rating for output circuit breakers satisfying the criteria for both. Rating is based on 100% of output current for a 100% breaker.

Table G. Maximum Output Circuit Breaker Ratings

Powerware 9315 Switchboard System Bypass module

 

SSBM Model

 

2500

 

3000

 

4000

 

 

 

SSBM

2500

 

3000

 

4000

SMB

2500

 

3000

 

4000

15.In the Parallel Capacity/Redundant System, each UPS module, Switchboard System Bypass Module (SSBM), SSBM breakers, and optional equipment are crated separately for shipping.

16.Do not tilt cabinets more than ¦10˚during handling.

17.Dimensions are in millimeters (inches).

DESCRIPTION:

INSTALLATION NOTES

DRAWING NO:

164201373---1

 

SHEET: 5 of 6

 

 

 

A---6

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

 

164201373 Rev. A 092402

Page 162
Image 162
Powerware 9315s Table E. Maximum Bypass Input Circuit Breaker Ratings, Table G. Maximum Output Circuit Breaker Ratings