Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9315 Switchboard System Bypass Module (SSBM):3P3W
(Output Neutral Not Used)
|
|
| Units |
| Rating |
| |
| Ratings |
| SSBM Model | 2500 | 3000 | 4000 | |
|
|
| Maximum Amps | 2500 | 3000 | 4000 | |
AC | AC Input from UPS to SSBM CBS Breaker |
| AWG or | Refer to Table R for minimum | |||
INPUT | Minimum conductor size, 3∅, (1) neutral, (1) gnd | A | kcmil(ea) | conductor sizes. |
| ||
(Note 5) | (number per ∅ and neutral) |
|
|
|
| ||
AC | AC Input to SSBM Bypass |
| AWG or | 500 | 500 | 500 | |
Full Load Current minimum conductor size, | B | kcmil(ea) | (6) | (7) | (9) | ||
INPUT | |||||||
3∅, (1) gnd (number per ∅) |
|
|
|
| |||
AC | AC Input to optional SMB Bypass |
| AWG or | 500 | 500 | 500 | |
INPUT | Full Load Current minimum conductor size, | C | kcmil(ea) | (6) | (7) | (9) | |
(Note 2) | 3∅, (1) gnd (number per ∅) |
|
|
|
| ||
AC | AC Output from SSBM to Load Bank |
| AWG or | 500 | 500 | 500 | |
Full Load Current minimum conductor size, | D | kcmil(ea) | (6) | (7) | (9) | ||
OUTPUT | |||||||
3∅, (1) gnd (number per ∅) |
|
|
|
| |||
| AC Output from SSBM or optional SMB to |
| AWG or | 500 | 500 | 500 | |
AC | Critical Load |
| kcmil(ea) | (6) | (7) | (9) | |
OUTPUT | Full Load Current minimum conductor size, | E |
|
|
|
| |
| 3∅, (1) gnd (number per ∅) |
|
|
|
| ||
|
|
|
|
|
|
Table B. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9315 Switchboard System Bypass Module (SSBM):3P4W
(Output Neutral Used)
|
|
| Units |
|
| Rating |
| |
| Ratings |
| SSBM Model |
| 2500 | 3000 | 4000 | |
|
|
| Maximum Amps |
| 2500 | 3000 | 4000 | |
AC | AC Input from UPS to SSBM CBS Breaker | A | AWG or | Refer to Table R for minimum | ||||
INPUT | Minimum conductor size, |
| kcmil(ea) | conductor sizes. |
| |||
(Note 5) | 3∅, (1) neutral, (1) gnd (number per ∅ and neutral) |
|
|
|
|
| ||
AC | AC Input to SSBM Bypass | B | AWG or |
| 500 | 600 | 600 | |
Full Load Current minimum conductor size, | kcmil(ea) |
| (7) | (8) | (11) | |||
INPUT | 3∅, (1) neutral, (1) gnd (number per ∅ and neutral) |
|
|
|
|
| ||
|
|
|
|
|
| |||
AC | AC Input to optional SMB Bypass | C | AWG or |
| 500 | 600 | 600 | |
INPUT | Full Load Current minimum conductor size, | kcmil(ea) |
| (7) | (8) | (11) | ||
|
| |||||||
(Note 12) | 3∅, (1) neutral, (1) gnd (number per ∅ and neutral) |
|
|
|
|
| ||
AC | AC Output from SSBM to Load Bank | D | AWG or | B | 500 | 600 | 600 | |
Full Load Current minimum conductor size, | kcmil(ea) | (7) | (8) | (11) | ||||
OUTPUT |
|
| ||||||
3∅, (1) neutral, (1) gnd (number per ∅ and neutral) |
|
|
|
|
| |||
|
|
|
|
|
| |||
| AC Output from SSBM or optional SMB to | E | AWG or |
| 500 | 600 | 600 | |
AC | Critical Load | kcmil(ea) |
| (7) | (8) | (11) | ||
OUTPUT | Full Load Current minimum conductor size, |
|
|
|
|
|
|
3∅, (1) neutral, (1) gnd (number per ∅ and neutral)
NOTE: Callout letters A , B ,C ,D , and E map to drawing
DESCRIPTION:
INSTALLATION NOTES
DRAWING NO: | SHEET: 1 of 6 |
|
|
|
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM | ||
| 164201373 Rev. A 092402 |