Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9315 Switchboard System Bypass Module (SSBM):3P3W

(Output Neutral Not Used)

 

 

 

Units

 

Rating

 

 

Ratings

 

SSBM Model

2500

3000

4000

 

 

 

Maximum Amps

2500

3000

4000

AC

AC Input from UPS to SSBM CBS Breaker

 

AWG or

Refer to Table R for minimum

INPUT

Minimum conductor size, 3, (1) neutral, (1) gnd

A

kcmil(ea)

conductor sizes.

 

(Note 5)

(number per and neutral)

 

 

 

 

AC

AC Input to SSBM Bypass

 

AWG or

500

500

500

Full Load Current minimum conductor size,

B

kcmil(ea)

(6)

(7)

(9)

INPUT

3, (1) gnd (number per )

 

 

 

 

AC

AC Input to optional SMB Bypass

 

AWG or

500

500

500

INPUT

Full Load Current minimum conductor size,

C

kcmil(ea)

(6)

(7)

(9)

(Note 2)

3, (1) gnd (number per )

 

 

 

 

AC

AC Output from SSBM to Load Bank

 

AWG or

500

500

500

Full Load Current minimum conductor size,

D

kcmil(ea)

(6)

(7)

(9)

OUTPUT

3, (1) gnd (number per )

 

 

 

 

 

AC Output from SSBM or optional SMB to

 

AWG or

500

500

500

AC

Critical Load

 

kcmil(ea)

(6)

(7)

(9)

OUTPUT

Full Load Current minimum conductor size,

E

 

 

 

 

 

3, (1) gnd (number per )

 

 

 

 

 

 

 

 

 

 

Table B. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9315 Switchboard System Bypass Module (SSBM):3P4W

(Output Neutral Used)

 

 

 

Units

 

 

Rating

 

 

Ratings

 

SSBM Model

 

2500

3000

4000

 

 

 

Maximum Amps

 

2500

3000

4000

AC

AC Input from UPS to SSBM CBS Breaker

A

AWG or

Refer to Table R for minimum

INPUT

Minimum conductor size,

 

kcmil(ea)

conductor sizes.

 

(Note 5)

3, (1) neutral, (1) gnd (number per and neutral)

 

 

 

 

 

AC

AC Input to SSBM Bypass

B

AWG or

 

500

600

600

Full Load Current minimum conductor size,

kcmil(ea)

 

(7)

(8)

(11)

INPUT

3, (1) neutral, (1) gnd (number per and neutral)

 

 

 

 

 

 

 

 

 

 

 

AC

AC Input to optional SMB Bypass

C

AWG or

 

500

600

600

INPUT

Full Load Current minimum conductor size,

kcmil(ea)

 

(7)

(8)

(11)

 

 

(Note 12)

3, (1) neutral, (1) gnd (number per and neutral)

 

 

 

 

 

AC

AC Output from SSBM to Load Bank

D

AWG or

B

500

600

600

Full Load Current minimum conductor size,

kcmil(ea)

(7)

(8)

(11)

OUTPUT

 

 

3, (1) neutral, (1) gnd (number per and neutral)

 

 

 

 

 

 

 

 

 

 

 

 

AC Output from SSBM or optional SMB to

E

AWG or

 

500

600

600

AC

Critical Load

kcmil(ea)

 

(7)

(8)

(11)

OUTPUT

Full Load Current minimum conductor size,

 

 

 

 

 

 

3, (1) neutral, (1) gnd (number per and neutral)

NOTE: Callout letters A , B ,C ,D , and E map to drawing #164201373---3

DESCRIPTION:

INSTALLATION NOTES

DRAWING NO:

164201373---1

SHEET: 1 of 6

 

 

 

A---2

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

 

164201373 Rev. A 092402

Page 158
Image 158
Powerware 9315s manual Powerware 9315 Switchboard System Bypass Module SSBM3P3W, Installation Notes